Users Manual 
10 
Description of Functions 
The functions are selected with the central rotary switch. Measurement values are shown 
on a liquid crystal display with correct decimal point and unit. Additional special 
characters indicate measurement mode, operating condition, and error messages. 
The Tester includes these measurement functions: 
  Earthing Resistance (R
E
The earthing resistance is determined by a 3-pole or 
4-pole current and voltage measurement. The 
measuring voltage is a square pulse ac voltage with 
48 / 20 V and a frequency of 94, 105, 111 or 128 Hz. 
The frequency can be selected manually or 
automatically (AFC). 
  Selective Measurement of 
Earthing (R
E
 
Measurement of a single earth electrode in a mesh 
operated (parallel) earthing system. The current flowing 
through the single earth electrode is measured with an 
external current transformer. 
  Low Battery Indicator 
Battery voltage is low, replace batteries.