When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval
t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED
illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted
before the expiry of the interval t, the interval already expired is erased and is restarted when the supply
voltage is next applied.
Functions
ON Delay (Er)
The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the
control contact S is closed, the output relay R switches into on-position (yellow LED illuminated). If the
control contact is opened, the set interval t begins (green LED flashes). After the interval t has expired
(green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated).
If the control contact is closed again before the interval t has expired, the interval already expired is
erased and restar
.
t at the the next opening of control contact S
OFF Delay with control input (R)
The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the
control contact S is closed, the output relay R switches into on-position (green LED U/t illuminated) and
the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay switches into off-position (yellow LED not illuminated). During the interval,
the control contact can be operated any number of times. A further cycle can only be started when the
cycle run has been completed.
Single shot leading edge with control input (Ts)
Single shot trailling edge with control input ( a)
T
The supply voltage U must be constantly applied to the device (green LED U/t illuminated). Closing the
control contact S has no influence on the condition of the output R. When the control contact is opened,
the output relay switches into on-position (yellow LED illuminated) and the set interval t begins (green
LED U/t flashes). After the interval t has expired (green LED U/t illuminated), the ouput relay switches
into off-position (yellow LED not illuminated). During the interval, the control contact can be operated
any number of times. A further cycle can only be started when the cycle run has been completed.
ON delay with control input (Es)
The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the
control contact S is closed, the set interval t begins (green LED U/t flashes). After the interval t has
expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated).
This status remains until the control contact is opened again. If the control contact is opened before the
interval t has expired , the interval already expired is erased and is restarted with the next cycle.
Single shot leading edge voltage controlled (
)
Em
When the supply voltage U is applied, the output relay R switches into on-position (yellow LED illuminated)
and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay switches into off-position (yellow LED not illuminated). This status remains
until the supply voltage is interrupted. If the supply voltage is interrupted before the interval t has expired,
the output relay switches into off-position
. The interval already
is erased and is restarted
when the supply voltage is next applied.
immediately
expired
Flash (Ef)
When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval
t has expired, the output relay R switches into on-position (yellow LED illuminated) and the set interval
t begins again. After the interval t has expired, the output relay switches into off-position (yellow LED
not illuminated). The output relay is triggered at a ratio of 1:1 until the supply voltage is interrupted.
Technical Data
Er
R
Ts
Ta
Es
EM
Ef
The function has to be set before connecting the relay to the supply voltage.
1. Functions
ON delay
OFF delay with control input
Single shot leading edge with control input
Single shot trailing edge with control input
ON delay with control input
Single shot leading edge voltage controlled
Flasher pause first
Time range
2. Time Ranges
Adjustment range
1s
10s
1min
10min
1h
10h
100h
50ms
500ms
3s
30s
3min
30min
5h
1s
10s
1min
10min
1h
10h
100h
Green LED U/t ON:
Green LED U/t flashes
Yellow LED R ON/OFF:
3. Indicators
indication of supply voltage
indication of time period
indication of relay output
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position:
any
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20
Tightening torque:
max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
4. Mechanical Design
5. Input Circuit
1 potential free change over contact
Rated voltage:
Switching capacity:
Fusing:
Mechanical life:
Electrical life:
Switching frequency:
Overvoltage category:
Rated surge voltage:
6. Output Circuit
250V AC
2000VA (8A / 250V)
8A fast acting
20 x 10 operations
2 x 10 operations at 1000VA resistive load
Max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
III. (in accordance with IEC 60664-1)
4kV
6
5
Input not potential free:
Loadable:
Max. line length:
Trigger level (sensitivity):
Min. control pulse length:
7. Control Input
Terminals A1-B1
Yes
10m
Automatic adaption to supply voltage
DC 50ms / AC 100ms
Base accuracy:
Adjustment accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence:
8. Accuracy
±1% of maximum scale value
<5% of maximum scale value
<0.5% or ±5ms
-
≤0.01% / °C
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
9. Ambient Conditions
-25 to +55°C
-25 to +70°C
-25 to +70°C
15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
2, if built-in 3
(in accordance with IEC 60664-1)
MCB-20
MCB-20
Er
R
Ts
Ta
Em
Ef
Supply voltage:
Terminals:
Tolerance:
Rated consumption:
Rated frequency:
Duty cycle:
Reset time:
Residual ripple for DC:
Drop-out voltage:
Overvoltage category:
Rated surge voltage:
12V to 240V AC/DC
A1(+)-A2
12V-10% to 240V+10%
4VA (1.5W)
AC 48 to 63Hz
100%
100ms
10%
>30% of minimum rated supply voltage
III (in accordance with IEC 60664-1)
4kV
Zaman Rölesi
Teknik Özellikler
Çok fonksiyonlu zamanlama
7 farklı mod
7 farklı zaman aralığı
Geniş aralıklı çalışma gerilimi
1 Enversör kontağı
17.5 mm genişlik
Er
R
Ts
Ta
Es
EM
Ef
Fonksiyonlar cihaza enerji verilmeden önce ayarlanmalıdır.
1. Fonksiyonlar
Çekmede gecikmeli
Kontrol girişli bırakmada gecikmeli
Basarken tetiklemeli bırakmada gecikmeli
Bırakırken
Kontrol girişli çekmede gecikmeli
Bırakmada gecikmeli
Flaşör
tetiklemeli bırakmada gecikmeli
Zaman aralığı
2. Zaman Aralığı
Ayar aralığı
1sn.
10sn.
1dk.
10dk.
1saat
10saat
100saat
50msn.
500msn.
3sn.
30sn.
3dk.
30dk.
5saat
1sn.
10sn.
1dk.
10dk.
1saat
10saat
100saat
Yeşil LED U/t ON:
Yeşil LED U/t flaşör:
Sarı LED R ON/OFF:
3. Gösterge
Besleme gerilimi göstergesi
Zaman peryot göstergesi
Röle çıkış göstergesi
IP40 koruma tipli kendiliğinden sönebilen plastik gövde
EN 50022'ye uyumlu TS 35 DIN montajı
Montaj yönü:
Farketmez
VBG 4'e uygun çarpma-korumalı giriş (PZ1 gerekli), IP20 tipi koruma
Sıkma torku:
en fazla 1Nm
Giriş alternatifleri:
1 x 0.5 ile 2.5mm² çok telli kablo ucu
1 x 4mm² çok telli olmayan kablo ucu
2 x 0.5 to 1.5mm² çok teli olan/olmayan kablo ucu
2 x 2.5mm² esnek, çok telli olmayan (flexible) kablo ucu
4. Mekanik Tasarım
Besleme gerilimi:
Terminal:
Tolerans:
Güç tüketimi:
Frekans:
Görev süresi:
Reset süresi:
DC'ye geçişte dalgalanma miktarı:
Gerilim düşüm oranı:
Aşırı gerilim sınıfı:
Anlık (surge) darbe gerilimi:
5. Giriş Devresi
12V to 240V AC/DC
A1(+)-A2
12V için -%10 ile 240V için +%10
4VA (1.5W)
AC'de 48Hz ile 63Hz arası
%100
100msn
%10
Minimum besleme geriliminde >%30
III (IEC 60664-1'e uygun)
4kV
1 adet boş çıkış kontağı (enversör)
Gerilim:
Açma Kapasitesi:
Sigorta:
Mekanik ömür:
Elektriksel ömür:
Anahtarlama frekansı:
Aşırı gerilim sınıfı:
Anlık (surge) darbe gerilimi:
6. Çıkış Devresi
250V AC
2000VA (8A / 250V)
8A hızlı açma
20 x 10 işlem
1000VA yük altında
100VA altında max. 60/dk.
1000VA altında max. 6/dk.
III. (IEC 60664-1'e uygun)
4kV
6
2 x 10 işlem
5
Boş olmayan girişler:
Yük bağlama:
Max. kablo mesafesi:
Tetikleme seviyesi (hassasiyet):
Min. kumanda giriş sinyal süresi:
7. Kumanda Girişi
Temel doğruluk:
Ayar doğruluğu:
Tekrarlama doğruluğu:
Gerilim etkisi:
Sıcaklık etkisi:
8. Doğruluk
±1% için maximum skala değeri
<5% için maximum skala değeri
<0.5% veya ±5msn
-
≤0.01% / °C
Ortam sıcaklığı:
Saklama sıcaklığı:
Taşıma sıcaklığı:
Bağıl nemlilik:
Kirlilik değeri:
9. Ortam koşulları
A1-B1
Evet
10m
Besleme gerilimine uygun otomatik ayarlama
DC'de 50msn., AC'de 100msn.
-25 ile +55°C
-25 ile +70°C
-25 ile +70°C
15% ile 85% (IEC 60721-3-3'e uygun)
2, eğer iç montajlı ise 3 (IEC 60664-1'e uygun)
Besleme girişine 'U' gerilimi uygulandığında, 't' set süresi başlatılır (Yeşil LED U/t yanıp söner). 't' set
süresinin bitmesinin ardından (Yeşil LED U/t sürekli yanar) R röle çıkışı ON konumuna geçer (Sarı LED
yanar). Cihazın besleme gerilimi kesilene kadar röle çekili konumda kalır. 't' set süresi bitmeden önce
besleme gerilimi kesilirse sayılmış zaman aralığı silinir ve besleme gerilimi tekrar uygulandığında 't' set
süresi saymaya başlar.
Fonksiyonlar
Çekmede gecikmeli (Er)
Cihaza 'U' besleme gerilimi sürekli olarak uygulanmalıdır (Yeşil LED U/t yanar). S kumanda kontağı
kapandığında, R çıkış rölesi ON konumuna geçer (Sarı LED yanar). Eğer kumanda kontağı
açılırsa, 't' set süresi başlatılır (Yeşil LED U/t yanıp sönecektir). 't' süresinin bitiminin ardından Yeşil
LED U/t sürekli yanar) röle çıkışı OFF konumuna geçecektir (Sarı LED söner). Eğer kumanda
kontağı 't' süresi bitmeden önce tekrar kapanırsa, sayılan zaman aralığı silinecek ve kumanda kontağı
açıldığında 't' set süresi başlayacaktır.
Kontrol girişli bırakmada gecikmeli (R)
Cihaza 'U' besleme gerilimi sürekli olarak uygulanmalıdır (Yeşil LED U/t yanar). S kumanda kontağı
kapandığında, R çıkış rölesi ON konumuna geçer (Sarı LED yanar) ve 't' set süresi başlar (Yeşil LED
U/t yanıp söner). 't' set süresi bittiğinde (Yeşil LED U/t sürekli yanar) röle çıkışı OFF konumuna
geçer (Sarı LED söner). 't' set süresince, kumanda kontağı kullanımı döngüyü etkilemez, 't' set süresi
bittikten sonra kumanda kontağı bir sonraki döngüyü başlatır.
Basarken tetiklemeli bırakmada gecikmeli (Ts)
Bırakırken tetiklemeli bırakmada gecikmeli ( a)
T
Cihaza 'U' besleme gerilimi sürekli olarak uygulanmalıdır (Yeşil LED U/t yanar). S kumanda kontağının
kapanması cihazın konumunu etilemez. Kumanda kontağının açılmasıyla R çıkış rölesi ON konumuna
geçer (Sarı LED yanar) ve 't' set süresi başlar (Yeşil LED U/t yanıp söner). 't' süresi bittiğinde (Yeşil LED
U/t sürekli yanar) röle çıkışı OFF konumuna geçer (Sarı LED söner). Sayma süresince, kumanda kontağı
birkaç defa kullanılabilir. 't' set süresince, kumanda kontağı kullanımı döngüyü etkilemez, 't' set süresi
bittikten sonra kumanda kontağı bir sonraki döngüyü başlatır.
Kontrol girişli çekmede gecikmeli (Es)
Cihaza 'U' besleme gerilimi sürekli olarak uygulanmalıdır (Yeşil LED U/t yanar). S kumanda kontağı
kapandığında, 't' set süresi başlar (Yeşil LED U/t yanıp söner). 't' süresinin bittiğinde (Yeşil LED U/t
sürekli yanar) R röle çıkışı ON konumuna geçer (Sarı LED yanar). Cihazın besleme gerilimi kesilene
kadar veya 'S' kontağı açılana kadar röle konumunu korur. Eğer kumanda kontağı 't' set süresinden
önce açılırsa sayılan zaman aralığı silinir ve 'S' kumanda kontağı tekrar kapandığında süre tekrar
başlar.
B
(
)
ırakmada gecikmeli Em
Besleme girişine 'U' gerilimi uygulandığında, R çıkış rölesi ON konumuna geçer (Sarı LED yanar) ve
't' set süresi başlar (Yeşil LED U/t yanıp söner). 't' süresi bittiğinde (Yeşil LED U/t sürekli yanar) R Röle
çıkışı OFF konumuna geçer (Sarı LED söner). Cihazın besleme gerilimi kesilene kadar röle konumunu
korur. 't' set süresi bitmeden önce besleme gerilimi kesilirse sayılmış zaman aralığı silinir ve besleme
gerilimi tekrar uygulandığında 't' set süresi saymaya başlar.
Flaşör (Ef)
Besleme girişine 'U' gerilimi uygulandığında, 't' set süresi başlar (Yeşil LED U/t yanıp söner). 't' set
süresi bittiğinde R röle çıkışı ON konumuna geçer (Sarı LED yanar) 't' set süresi tekrar başlayacaktır.
't' set süresi bittiğinde (Yeşil LED U/t yanıp söner) R röle çıkışı OFF konumuna geçer (Sarı LED söner).
Besleme gerilimi kesilene kadar röle çıkışı 1:1 oranında tetiklenecektir.
M1183 KTL / Rev.2
"Bu ürün, 30.05.2008 tarih ve 26891 sayılı resmi gazetede yayınlanan EEE Yönetmeliğinin Madde 2 ve Ek-1A madde 9 kapsamındadır."