Crydom D1D12 Solid State Relay, DC Output D1D12 Datenbogen

Produktcode
D1D12
Seite von 5
Series 1-DC 
 
 
• D1D to  D5D series  SSRs; MOSFET  output  
• Ratings from 7A to 40A @ 200 VDC, and from 7A to 10A @ 500 VDC  
• DC Control  
• Relays are easily paralleled for higher-current applications 
 
PRODUCT SELECTION
Load Voltage
7A
10A
12A
20A
40A
100 VDC
D1D07
D1D12
D1D20
D1D40
200 VDC
D2D07
D2D12
D2D40
400 VDC
D4D07
D4D12
500 VDC
D5D07
D5D10
OUTPUT SPECIFICATIONS (1)
Description
7A
12A
20A
40A
7A
12A
40A
7A
12A
7A
10A
Operating Voltage Range
0-100
0-100
0-100
0-100
0-200
0-200
0-200
0-400
0-400
0-500
0-500
Maximum Off-State Leakage Current @ Rated Voltage [mA]
0.1
0.2
0.3
0.3
0.1
0.3
0.3
0.3
0.3
0.2
0.3
Maximum Load Current (3) [Adc]
7
12
20
40
7
12
40
7
12
7
10
Minimum Load Current [mA]
0
0
0
0
0
0
0
0
0
0
0
Maximum Surge Current [Adc] (10ms)
15
28
42
106
22
27
106
17
36
19
29
Maximum On-State Voltage Drop @ Rated Current [Vdc]
2.0
1.6
2.1
2.1
2.0
2.8
2.1
4.2
4.2
5.7
5.5
Thermal Resistance Junction to Case (Rjc) [°C/W]
2.2
1.34
1.06
0.83
1.5
1.06
0.83
1.06
0.8
1.0
0.8
Maximum On-State Resistance [RDS-ON][Ohms]
0.29
0.13
0.10
0.05
0.29
0.23
0.05
0.6
0.35
0.8
0.55
INPUT SPECIFICATIONS (1)
Description
DC Control
Control Voltage Range 
3.5-32 VDC
Minimum Turn-On Voltage 
3.5 VDC
Minimum Turn-Off Voltage
1.0 VDC
Maximum Input Current  (1-DC only)
1.6 mA (5 VDC), 28 mA (32 VDC)
Nominal Input Impedance
See Note 4
Maximum Turn-On Time  [µsec] 
100
Maximum Turn-Off Time  [msec] 
1.0
GENERAL SPECIFICATIONS
Description
Parameters
Dielectric Strength, Input/Output/Base (50/60Hz)
2500 VRMS
Minimum Insulation Resistance (@ 500 V DC)
10
9
 Ohm
Maximum Capacitance, Input/Output
50 pF
Ambient Operating Temperature Range
-20 to 80°C
Ambient Storage Temperature Range
-20 to 125 °C
Weight (typical)
3.0 oz (86.5g)
Encapsulation
Thermally conductive Epoxy
Terminals
Screws and Saddle Clamps Furnished, Unmounted
Recommended Terminal Screw Torque Range:
6-32 Screws - 10 in lbs. 8-32 and 10-32 Screws -20 in. lbs. (Screws dry without grase)
 
GENERAL NOTES 
1) All parameters at 25°C and per section unless otherwise specified. 
2) Dielectric strength and insulation resistance are measured between input and output 
3) Heat sinking required, for derating curves see page 3. 
4) Input circuitry version incorporates active current limiter.