DERATING CURVES
DRxxx06
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0
10
20
30
40
50
60
Ambient Temperature (°C)
Lo
ad
 C
u
rr
en
t (A
m
p
s)
70
80
Multiple units, no minimum spacing between components
Installed single unit, distance to adjacent components ≥ 11 mm
for DRxxx06 and ≥ 18 mm for DRxxx12 & DRDxxD06
DRxxx12 & DRDxxD06
0
10
20
30
40
50
60
0.0
2.0
4.0
6.0
8.0
10.0
12.0
Ambient Temperature [°C]
Loa
d
 Cu
rre
n
(Combined for Dual) [Amps]
70
80
For 
DRxxx06 or DRxxx12 versions
For 
DRDxxD06 versions
AC SUPPLY
AC SUPPLY
DC CONTROL
(C)
(D, E)
+A
-A
+B
-B
Load B
Load A
1/A1
2/A2
1/A1
2/A2
3/B1
4/B2
INPUT
ST
AT
US
INPUT
ST
AT
US
(D, E)
DC/AC CONTROL
VOLTAGE
DC/AC SUPPLY
Load
+3/A1
+3/A1
4/A2
4/A2
2/T1
1/L1
INPUT
ST
A
TUS
WIRING DIAGRAMS
No grounding wire required. DC inductive loads must be diode suppressed.
4 Pin connector for dual channel ouput only. Matting connector: MOLEX 050579404 or equivalent.
(B)
(C)
4 Terminal screws Pozidriv #1, 3/16 in [4.8 mm].
Minimum wire strip lenght 0.20 in [5.1 mm], maximum 0.28 in [7.1 mm].
(D)
(E)
(B)
WARNING
RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
• The product's side panels may be hot, allow the product to cool before touching.
• Follow proper mounting instructions including torque values.
• Do not allow liquids or foreign objects to enter this product.
Failure to follow these instructions can result in serious injury, or equipment damage.
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Turn off power supply before working on this equipment.
Failure to follow these instructions will result in death or serious injury.
DANGER