Crydom Solid State Relay H16Wd6075G H16WD6075G Datenbogen

Produktcode
H16WD6075G
Seite von 5
H16WD Series
 
• Ratings from 25A to 90A @ 48-660 V AC 
• 1600 Volt Blocking  
• SCR output for heavy industrial loads  
• DC control  
• Zero-crossing (resistive loads) or random-fire (inductive loads) output 
• Optional LED Status Indicator 
 
PRODUCT SELECTION
Control Voltage
25A
50A
75A
90A
4-32 Vdc
H16WD6025
H16WD6050
H16WD6075
H16WD6090
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description
25A
50A
75A
90A
Operating Voltage (47-440Hz) [Vrms]
48-660
48-660
48-660
48-660
Transient Overvoltage [Vpk]
1600
1600
1600
1600
Rated Load Current (2) [Arms]
25
50
75
90
Rated Load Current {UL508 Motor Controller} (2) [Arms]
10
20
30
45
Minimum Load Current [mArms]
150
150
150
150
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
1.0
1.0
1.0
1.0
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3)
500
500
500
500
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
239/250
597/625
954/1000
1145/1200
Maximum I²t for Fusing (50/60Hz) [A² sec]
285/259
1779/1621
4555/4150
6560/5976
Thermal Resistance Junction to Case (Rjc) [°C/W]
1.02
0.63
0.31
0.28
Maximum On-State Voltage Drop @ Rated Current [Vpk]
1.6
1.6
1.6
1.6
HP rating UL 508/IEC60947[HP (KW)]: 240 VAC
1.5 (1.1)
3 (2.2)
5 (3.7)
7.5 (5.6)
HP rating UL 508/IEC60947[HP (KW)]: 380 VAC
2 (1.5)
5 (3.7)
7.5 (5.6)
15 (11.2)
HP rating UL 508/IEC60947[HP (KW)]: 480 VAC
3 (2.2)
5 (3.7)
10 (7.4)
20 (14.9)
HP rating UL 508/IEC60947[HP (KW)]: 600 VAC
3 (2.2)
10 (7.4)
15 (11.2)
25 (18.6)
Wire Size max (solid/stranded) [AWG/ IEC mm²]
2 x 8/8.4
2 x 8/8.4
2 x 8/8.4
2 x 8/8.4
Output Terminal Screw Torque Range [in lb (Nm)
18-20 (2-2.2)
18-20 (2-2.2)
18-20 (2-2.2)
18-20 (2-2.2)