Crydom CTRC6025 3-Phase Solid State Relay CTRC6025 Datenbogen

Produktcode
CTRC6025
Seite von 5
INPUT SPECIFICATIONS (1)
Description
CTRD6025
CTRB6025
CTRC6025
Control Voltage Range 
4.0-32 VDC
90-140 Vrms
180-280 Vrms
Minimum Turn-On Voltage
4.0 VDC
90 Vrms
180 Vrms
Minimum Turn-Off  Voltage
1.0 VDC
10 Vrms
10 Vrms
Minimum Input Current  (4)
50 mA
15 mA
19 mA
Maximum Input Current  (4)
62 mA
19 mA
24 mA
Maximum Turn-On Time  [msec] (5)
1/2 Cycle
20
20
Maximum Turn-Off Time  [msec] 
1/2 Cycle
30
30
Min/Max stranded/solid wire
24/16 AWG
24/16 AWG
24/16 AWG
GENERAL SPECIFICATIONS
Description
CTRD6025
CTRB6025
CTRC6025
Dielectric Strength, Input/Output/Base (50/60Hz)
4000Vrms
4000Vrms
4000Vrms
Minimum Insulation Resistance (@ 500 V DC)
10
9
 Ohms 
10
9
 Ohms 
10
9
 Ohms 
Maximum Capacitance, Input/Output
8 pF
8 pF
8 pF
Ambient Operating Temperature Range
-20ºC to 80ºC
-20ºC to 80ºC
-20ºC to 60ºC
Ambient Storage Temperature Range
-40ºC to 100ºC
-40ºC to 100ºC
-40ºC to 100ºC
Status Indicator Display
Green LED
Green LED
Green LED
Weight (typical)
21.2 oz. (600g)
21.2 oz. (600g)
21.2 oz. (600g)
Terminals
Box Clamp Type
Box Clamp Type
Box Clamp Type
Recommended Terminal Screw Torque Range:
5.0-6.0 in lb (0.6-0.7 Nm)
5.0-6.0 in lb (0.6-0.7 Nm)
5.0-6.0 in lb (0.6-0.7 Nm)
Min. Side by Side Spacing
0.8 inch (20mm)
0.8 inch (20mm)
0.8 inch (20mm)
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified. 
2) See Derating Curves 
3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 
4) Turn-on time for DC control random turn-on versions is 0.02 msec 
5) Input circuitry incorporates active current limiter. 
 
MECHANICAL SPECIFICATIONS