Crydom Din Rail Plug-In Base Drsed DRSED Merkblatt

Produktcode
DRSED
Seite von 2
AC/DC Output Pluggable SSRs
ED Series
PART NUMBER NOMENCLATURE
Required for valid part number
For options only and not required
 for valid part number
MOUNTING INSTRUCTIONS
Please read all installation instructions before using ED Series SSRs.
Select mounting type. DIN rail mountable (DRSED) and PCB 
mountable (PCBSED) sockets are sold separately.
fig. 2 
PCBSED Socket Mounting
TO LOCK
ED Series 
SSR
fig. 1 
DRSED Socket Mounting/Dismounting
TO REMOVE FROM
DIN RAIL
TO INSTALL ON DIN RAIL
TO UNLOCK
ED Series 
SSR
Insert ED series SSR into DRSED socket observing terminals’ 
orientation (fig. 1).
Secure ED SSR using latching mechanism on socket until you hear 
a clicking sound.
Install the ED series SSR / socket on the DIN rail as shown in fig.1
Wire the socket DRSED to the input/output side (fig. 5). 24 AWG 
minimum, 2 x 14 AWG (stranded/solid) maximum. Maximum 
recommended terminal screw torque 5.3-8.85 in lbs (0.60-1.2 N m) 
on input/output terminations. Choose wire gauge according to load 
current.
To retrieve the ED series SSR from socket, first unlock latching 
mechanism, as shown in fig.1, then gently pull the SSR.
Release DRSED socket from DIN rail using a screwdriver. See fig.1.
If multiple units are installed be sure to follow derating curve.
Mounting an ED series SSR using a DIN rail mountable socket:
Before mounting the ED series SSR into the PCBSED socket, first solder PCBSED socket onto PC board. 
When soldering the relay terminals, use a soldering iron of 30 to 60W, and quickly complete soldering (within 
approximately 3 seconds). Use a non-corrosive resin flux.
Insert ED series SSR into PCBSED socket observing terminals’ orientation (fig. 2).
Secure ED SSR using latching mechanism on socket until you hear a clicking sound.
To retrieve the ED series SSR from socket, first unlock latching mechanism, as shown in fig.2, then gently 
pull the SSR.
Mounting an ED series SSR using a PCB mountable socket:
The following deating curves must be observed before installation.
DERATING CURVES
(A)
(B)
(C)
6.0
5.0
4.0
3.0
2.0
1.0
10
20
30
40
50
60
70
80
0
Ambient Temperature (ºC)
Load Current (Amps)
ED24xxx
6.0
5.0
4.0
3.0
2.0
1.0
10
20
30
40
50
60
70
80
0
Ambient Temperature (ºC)
Load Current (Amps)
ED10x5 & ED06x5
Series
Operational Current
3: 3 Amps (not available with B & E suffixes)
5: 5 Amps
Output Voltage
06: 1-48 VDC (5 Amps only)
10: 1-80 VDC (5 Amps only)
24: 24-280 VAC
Control Voltage
B: 90-140 VAC *
C: 18-32 VDC
D: 3-15 VDC **
E: 18-36 VAC
F: 48-72 VDC
ED
24
C
5
Switching Mode
Blank: Zero Voltage Turn-On
(AC Output only)
R: Random Turn-On
(AC Output only)
R
  * 100-140 VAC range for ED24B5
**  5-15 VDC range for ED06/10D5
3 Amps
5 Amps