Crydom SOLID-STATE-RELAY DR48D03 DR48D03 Datenbogen

Produktcode
DR48D03
Seite von 7
INPUT SPECIFICATIONS (1)
Description
DRxxDxx
DRxxBxx
DRxxAxx
DRxxExx
Control Voltage Range (4)
4.0-32 VDC
90-140 Vrms
200-265 Vrms
18-36 Vrms
Minimum Turn-On Voltage
4.0 VDC
90 Vrms
200 Vrms
18 Vrms
Minimum Turn-Off  Voltage
1.0 VDC
10 Vrms
90 Vrms
4 Vrms
Minimum Input Current [mA] (5)
9
3
2.5
3.5
Maximum Input Current [mA]  (5)
11
5
3.3
8
Maximum Turn-On Time  (6) (7)
1/2 Cycle
20 msec
20 msec
20 msec
Maximum Turn-Off Time  (8)
1/2 Cycle
30 msec
30 msec
30 msec
Min/Max stranded/solid wire
22/16 AWG
22/16 AWG
22/16 AWG
22/16 AWG
GENERAL SPECIFICATIONS (1)
Description
Parameters
Dielectric Strength, Input to Output (50/60Hz)
4000Vrms (9)
 
 
Minimum Insulation Resistance (@ 500 V DC)
10
9
 Ohms 
Maximum Capacitance, Input/Output
10 pF
Ambient Operating Temperature Range
-30ºC to 80ºC
Ambient Storage Temperature Range
-30ºC to 100ºC
Recommended Terminal Screw Torque Range:
4.4-7.0 in lb (0.5-0.8 Nm)
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified. 
2) See Derating Curves 
2A) For AC output frequency is 47-63Hz 
3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 
4) DC control includes reverse polarity protection. 
5) Input circuitry incorporates active current limiter. 
6) Turn-on time for DC control random turn-on versions is 0.1 msec 
7) Turn-on time for DC output 600µsec 
8) Turn-off time for DC output 300µsec 
9) 2500 Vrms for DC output 
 
Standards of Compliance 
 
IEC 62314 
LC A, Resistive or Slightly Inductive Load Ratings: 3A @ 40°C ambient for DR24x03, 3A @ 40°C ambient for DR48x03 
 
LC B, Motor Loads Ratings: 0.18KW @ 240VAC for DR24x03 and 0.375KW @ 480VAC DR48x03 
 
 
Shock and Vibration (Applies to all part numbers) 
Vibration Resistance according to IEC 60068-2-6: 0.35mm and 0.75mm Amplitude over 10-55 Hz 
Shock Resistance according to IEC 60068-2-27: 15g/11ms 
 
EMC 
(Applies to all part numbers) 
IEC 61000-4-2 : Electrostatic Discharge – Level 3 
IEC 61000-4-4 : Electrically Fast Transients – Level 3 
IEC 61000-4-5 : Electrical Surges – Level 3