6.2 mm Base Terminal Block Design
5 & 24 VDC and 120 & 240 VAC Control Input Options
24 VDC @ 3.5 A, 48 VDC @ 100 mA and 240 VAC @ 2 A Operating Voltage Rating
Factory assembled ready to use assemblies for AC and DC output
Socket clip fits all standard 35 mm DIN rails
IP67-protected fully encapsulated SSRs
Yellow LED input status indicator
UL & cUL recognized SSRs & sockets, UL 100 K cycle extended endurance tested SSRs,
CE & RoHS compliant SSRs, sockets & assemblies
AC & DC Output
DRACN Series Assemblies
OUTPUT SPECIFICATIONS FOR ALL MODELS
DRA-CN024DXX
DRA-CN048DXX
DRA-CN240AXX
Operating Voltage
0-24 VDC
0-48 VDC
24-280 VAC (47-63 Hz)
Maximum Load Current @ 40°C
3.5 A
 100 mA
 2 A
Minimum Load Current [mA]
1
1
70
Maximum Blocking Voltage
30 VDC
60 VDC
600 VAC
Maximum Surge Current
9 A (10 ms)
300 mA (10 ms)
120/115 Apk (16.6/20 ms)
Maximum I²t for fusing (8.3/10 msec) [A² sec]
N.A.
N.A.
260/285
Typical On-State Voltage Drop @ Rated Current [V]
0.4
1.0
1.1 (peak)
Maximum Off-State Leakage Current @ Rated Voltage [mA]
0.001
0.001
4.0
Maximum PWM [Hz]
500
500
N.A.
Switch Configuration
Normally Open
Normally Open
Normally Open
INPUT SPECIFICATIONS FOR DRA-CN024DXX
DRA-CN024D05
DRA-CN024D24
DRA-CN024D120
DRA-CN024D240
Control Voltage Range
3-12 VDC
15-30 VDC
90-140 VAC
190-250 VAC
Min. Turn-On Voltage
3.0 VDC
15 VDC
90 VAC
190 VAC
Min. Turn-Off Voltage
1.5 VDC
12 VDC
31 VAC
60 VAC
Typical Input Current [mA]
10 mA ± 10% @ 5 VDC
9 mA ± 10% @ 24 VDC
3.4 mA ± 10% @ 120 VAC
3.4 mA ± 10% @ 240 VAC
Typical Turn-On Time
120 μsec
350 μsec
2 ms
3 ms
Typical Turn-Off Time
100 μsec
80 μsec
5 ms
6 ms
INPUT SPECIFICATIONS FOR DRA-CN048DXX
DRA-CN048D05
DRA-CN048D24
DRA-CN048D120
DRA-CN048D240
Control Voltage Range
3-12 VDC
16-30 VDC
100-140 VAC
190-250 VAC
Min. Turn-On Voltage
3.0 VDC
16 VDC
100 VAC
190 VAC
Min. Turn-Off Voltage
1.5 VDC
11 VDC
32 VAC
60 VAC
Typical Input Current [mA]
6 mA ± 10% @ 5 VDC
7 mA ± 10% @ 24 VDC
3.4 mA ± 10% @ 120 VAC
3.4 mA ± 10% @ 240 VAC
Typical Turn-On Time
20 μsec
20 μsec
1 ms
2 ms
Typical Turn-Off Time
130 μsec
130 μsec
5 ms
6 ms
INPUT SPECIFICATIONS FOR DRA-CN240AXX
DRA-CN240A05
DRA-CN240A24
DRA-CN240A120
DRA-CN240A240
Parameters
Parameters
Control Voltage Range
3-12 VDC
15-30 VDC
90-140 VAC
190-250 VAC
Min. Turn-On Voltage
3.0 VDC
15 VDC
90 VAC
190 VAC
Min. Turn-Off Voltage
2.0 VDC
10 VDC
60 VAC
175 VAC
Typical Input Current [mA]
15 mA ± 10% @ 5 VDC
7 mA ± 10% @ 24 VDC
4 mA ± 10% @ 120 VAC
3.6 mA ± 10% @ 230 VAC
Typical Turn-On Time
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
Typical Turn-Off Time
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
Overvoltage Category
Degree of protection (for SSR only)
Ambient Operating Temperature Range
-20 to 60°C
Dielectric Strength, Input/Output
2.5 KV
Maximum Capacitance, Input/Output
1.5 pF
Polution Degree
2
lll
Ambient Storage Temperature Range
-20 to 80 °C
Housing Material
UL 94 V0
IP67
GENERAL SPECIFICATIONS FOR ALL MODELS
GENERAL NOTES
All parameters at 25°C unless otherwise specified. 
See derating curves for more information.
Operating frequency higher than 500 Hz will damage SSR.
Turn-on time for random turn-on version is 0.1 msec. 
3.75 KV for CN048Dxx models.
(A)
(B)
(C)
(D)
(E)
(F)
CN Series SSR and DIN rail socket are sold separately or together as a DRACN Series assembly.
MECHANICAL SPECIFICATIONS FOR ALL MODELS
Dimensions (W x H x D)
6.1 mm x 93 mm x 80 mm
31 grs (0.067 lb)
Weight (Typical)
Max. Torque Output
Terminals
10 mm
5 - 7 in lb (0.56 - 0.8 Nm)
Max. Wire size Output
AWG #24-14 Solid. AWG #24-14 Stranded
(A)
(B)
(C)
(D)
(D)
(D)
(F)
(E)