Finder 49.52.7.024.0050 Relay Interface Module 2 changeovers 24 Vdc 49.52.7.024.0050 Datenbogen
![Finder](https://files.manualsbrain.com/attachments/2ff21089e5cc4b71108c7c1dd0c66b81ce9f009f/common/fit/150/50/80f54547e28bbe39d4385a567b8f6a2b4fcf8f94d8139f4e47302d525c77/brand_logo.gif)
Produktcode
49.52.7.024.0050
49.61/81-00x0 49.61/81-40x0
1 Pole relay interface module
AgCdO contacts for heavy duty switching
49.61-00x0 - 1 Pole 16 A (screw terminal)
49.81-00x0 - 1 Pole 16 A (screwless terminal)
49.81-00x0 - 1 Pole 16 A (screwless terminal)
AgSnO
2
contacts for heavy duty, high
current inrush switching
49.61-40x0 - 1 Pole 16 A (screw terminal)
49.81-40x0 - 1 Pole 16 A (screwless terminal)
49.81-40x0 - 1 Pole 16 A (screwless terminal)
•
15.5 mm wide
•
Ideal interface for PLC and electronic systems
•
AC coils & DC coils
•
Instant ejection of relay using plastic
retaining clip
•
Supply status indication and coil suppression
module
•
Identification labels
•
35 mm rail (EN 60715) mounting
1 CO (SPDT) 1 CO (SPDT)
16*/30 16*/100 (5 ms)
250/400 250/400
4,000 4,000
750 750
0.55 0.55
16/0.3/0.12 16/0.3/0.12
500 (5/5) 1,000 (10/10)
AgCdO AgSnO
2
12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
12 - 24 - 125 12 - 24 - 125
1.2/0.65/0.5 1.2/0.65/0.5
(0.8…1.1)U
N
(0.8…1.1)U
N
(0.73…1.5)U
N
/(0.8…1.5)U
N
(0.73…1.5)U
N
/(0.8…1.5)U
N
0.8 U
N
/0.4 U
N
0.8 U
N
/0.4 U
N
0.2 U
N
/0.1 U
N
0.2 U
N
/0.1 U
N
10 · 10
6
10 · 10
6
100 · 10
3
100 · 10
3
7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
6 (8 mm) 6 (8 mm)
1,000 1,000
–40…+70 –40…+70
IP 20 IP 20
•
1 pole, 16 A*
•
AgSnO
2
contact material
•
Screw terminal and screwless terminal
•
35 mm rail (EN 60715) mounting
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220V A
Minimum switching load mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (U
N
) V AC (50/60 Hz)
V DC
Rated power AC/DC/sens.DC VA (50 Hz)/W/W
Operating range AC
DC/sensitiv DC
Holding voltage AC/DC
Must drop-out voltage AC/DC
Technical data
Mechanical life cycles
Electrical life at rated load AC1 cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs) kV
Dielectric strength between open contacts V AC
Ambient temperature range °C
Protection category
Approvals relay (according to type)
8.xxx.4060 7.xxx.4050
9.xxx.4050
4
For outline drawing see page 8
49.61
Screw terminal
Screw terminal
49.81-00x0/40x0
Screwless terminal
Screwless terminal
•
1 pole, 16 A*
•
AgCdO contact material
•
Screw terminal and screwless terminal
•
35 mm rail (EN 60715) mounting
8.xxx.0060 7.xxx.0050
9.xxx.0050
Features
* For currents >10 A, contact terminals
must be connected in parallel
(21 with 11, 24 with 14, 22 with 12).
(21 with 11, 24 with 14, 22 with 12).
* For currents >10 A, contact terminals
must be connected in parallel
(21 with 11, 24 with 14, 22 with 12).
(21 with 11, 24 with 14, 22 with 12).
II-2014, www.findernet.com
49
SERIE S
49 Series - Relay interface modules 8 - 10 - 16 A
B