Phoenix Contact Surge protection connector PT 1X2-48DC-ST 2803658 2803658 Datenbogen

Produktcode
2803658
Seite von 7
Nov 13, 2013    3 / 7
Technical data
Protective circuit
Voltage protection level U
P
 (Core-Core)
≤ 120 V (C2 (10 kV/5 kA))
Voltage protection level U
P
 (Core-Earth)
≤ 450 V (C1 - 500 A (1X2-BE))
Voltage protection level U
P
 (Core-Earth)
≤ 550 V (C2 - 1 kA (1x2-BE))
Voltage protection level U
P
 (Core-Earth)
≤ 600 V (C2 - 5 kA (1X2-BE))
Response time tA (Core-Core)
≤ 1 ns
Response time tA (Core-Earth)
≤ 100 ns
Input attenuation aE, sym.
0.5 dB (≤ 2 MHz)
Input attenuation aE, sym.
0.5 dB (≤ 2 MHz / 50 Ω)
Input attenuation aE, sym.
0.2 dB (≤ 600 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
typ. 10 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 3.5 MHz
Capacity (Core-Core)
1 nF
Resistance in series
2.2 Ω (7-8/11-12)
Message: Surge protection fault
None
Max. required back-up fuse
500 mA (e.g. T ( IEC 127-2/III))
Surge carrying capacity in acc. with IEC 61643-21 (Core-Core) C2 (10 kV/5 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C2 (10 kV/5 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) D1 (2.5 kA)
Connection data
Connection method
Screw connection (in connection with the base element)
Connection type IN
PLUGTRAB plug-in system
Connection type OUT
PLUGTRAB plug-in system
Standards and Regulations
Standards/regulations
IEC 61643-21
Standards/regulations
DIN EN 61643-21
classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130807
eCl@ss 7.0
27130807
eCl@ss 8.0
27130807
ETIM
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943