Phoenix Contact Type 1 surge protection device VAL-MS-T1/T2 335/12.5/3+1 2800184 2800184 Datenbogen

Produktcode
2800184
Seite von 8
Nov 13, 2013    3 / 8
Technical data
Protective circuit
Voltage protection level U
P
 (L-PE)
≤ 2 kV
Voltage protection level U
P
 (N-PE)
≤ 1.7 kV
Residual voltage (L-N)
≤ 1.1 kV (at 10 kA)
Residual voltage (L-N)
≤ 1 kV (at 5 kA)
Residual voltage (L-N)
≤ 0.9 kV (at 3 kA)
Residual voltage (L-N)
≤ 1.2 kV (at I
n
)
Residual voltage (L-PE)
≤ 1.5 kV (at 10 kA)
Residual voltage (L-PE)
≤ 1.2 kV (at 5 kA)
Residual voltage (L-PE)
≤ 1.1 kV (at 3 kA)
Residual voltage (L-PE)
≤ 2 kV (at I
n
)
Residual voltage (N-PE)
≤ 0.5 kV (at 10 kA)
Residual voltage (N-PE)
≤ 0.5 kV (at 5 kA)
Residual voltage (N-PE)
≤ 0.4 kV (at 3 kA)
Residual voltage (N-PE)
≤ 0.6 kV (at I
n
)
Response time (L-N)
≤ 25 ns
Response time (L-PE)
≤ 100 ns
Response time (N-PE)
≤ 100 ns
Max. required backup fuse with branch wiring
160 A (gL/gG)
Max. required backup fuse with V-type through wiring
80 A (gL/gG / with 16 mm²)
Short-circuit resistance I
P
 with max. backup fuse (effective)
25 kA
Follow current quenching capacity If (N-PE)
100 A (264 V AC)
Connection, protective circuit
Connection method
Screw connection
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
16 mm
Conductor cross section stranded min.
1.5 mm²
Conductor cross section stranded max.
25 mm²
Conductor cross section solid min.
1.5 mm²
Conductor cross section solid max.
35 mm²
Conductor cross section AWG/kcmil min.
15
Conductor cross section AWG/kcmil max
2
Standards and Regulations
Standards/regulations
IEC 61643-1 2005
Standards/regulations
EN 61643-11/A11 2007