Technical data
General
Pollution degree
2
Mounting type
On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Design
LSA-PLUS module
Number of positions
2
Direction of action
Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 1.10
Protective circuit
IEC test classification
B2
IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
VDE requirement class
B2
VDE requirement class
C1
VDE requirement class
C2
VDE requirement class
C3
VDE requirement class
D1
Nominal voltage U
N
12 V DC
Maximum continuous operating voltage U
C
± 15 V DC
Maximum continuous operating voltage U
C
10 V AC
Maximum continuous voltage U
C
 (wire-ground)
± 15 V DC
Maximum continuous voltage U
C
 (wire-ground)
10 V AC
Nominal current I
N
380 mA (25 °C)
Operating effective current I
C
 at U
C
≤ 5 µA
Residual current I
PE
≤ 2 µA
Nominal discharge current I
n
 (8/20) µs (Core-Earth)
5 kA
Total surge current (8/20) µs
10 kA
Total surge current (10/350) µs
2.5 kA
Max. discharge current I
max
 (8/20) µs maximum (Core-Earth)
10 kA (in total)
Nominal pulse current Ian (10/1000) µs (Core-Earth)
100 A
Impulse discharge current (10/350) µs, peak value l
imp
1 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 28 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 22 V
Residual voltage at I
n
, (conductor-ground)
≤ 32 V
Residual voltage with Ian (10/1000)µs (conductor-ground)
≤ 18 V
Voltage protection level U
P
 (Core-Earth)
≤ 60 V (C2, 10 kV/5 kA, spike)
Voltage protection level U
P
 (Core-Earth)
≤ 30 V (C3, 7.5 kV/100 A, spike)
Response time tA (Core-Earth)
≤ 1 ns
Input attenuation aE, asym.
0.3 dB (≤ 400 kHz)