Finder Electricity meter (3-phase) digital 65 A MID-approved: Yes 7E.46.8.400.0012 7E.46.8.400.0012 Datenbogen

Produktcode
7E.46.8.400.0012
Seite von 8
10/65
5/6
0.04
0.01
0.5...65
0.05...6
1,950 (10 ms)
180 (10 ms)
3 x 230
3 x 230
(0.8...1.15)U
N
(0.8...1.15)U
N
50/60
50/60
1.5
1.5
Seven digit counter, LCD with backlight
999,999.9/0.01 **
9,999,999/0.1 ***
100
10
5...30 5...30
20
20
10
10
1,000
10
30
30
100
100
1,000
1,000
1 / B
1 / B
–10…+55 °C
–10…+55 °C
II
II
IP 50/IP 20
IP 50/IP 20 
2
Features
kWh Energy meter
3-phase with multi-functional LC-Display
Type 7E.46-0002  10(65)A - Single and Dual tariff
Type 7E.56-0000    5  (6)A - for current transformer 
up to 1,500 A
Complies with EN 62053-21 and EN 50470
Display indicates total consumption, partial 
consumption (this value is resettable), 
instantaneous power per phase or all phases, 
voltage per phase, current per phase
ERROR-Display, in case of missing phase or 
wrong current direction
Seven digit counter, LCD with backlight
Accuracy class: 1/B
Easy to operate by two control keys
LC-Display can be read twice within a period 
of 10 days following the loss of supply voltage
Protection class II
Pulse output for remote energy management; 
SO interface (open collector) according 
DIN 43864 to link the energy meter to a 
centrally located monitoring/management system
Tamper-proof cover with lead seal facility 
available as an accessory
35 mm rail (EN 60715) mount
MID compliant version (50 Hz only) available
Nominal current 10 A (65 A Maximum)
3-phase
Single and Dual tariff (Day and Night)
70 mm wide
Nominal current 5 A (6 A Maximum)
3-phase
Usable with current transformer up to 1,500 A
14 selectable Current Transformer ratios
70 mm wide
Specification
Nominal/Maximum current
A
Minimum measured current
A
Current range (within accuracy class)
A
Maximum peak current       
A                        
Supply (& monitored) voltage (U
N
)
V  AC
Operating range                                                   
Frequency
Hz
Power consumption per phase
W
Display (digit height 6 mm)
Max. totalising count/Min. increment
kWh  
LCD-segment pulses per kWh
Open collector- output specification (SO+/SO–)
Voltage (external supply)
V DC
Maximum current
mA
Maximum leakage current @30 V/25 °C
μA
Pulses per kWh
Pulse length
ms
Internal series resistance
Ω
Maximum Cable length @30 V/20 mA
m
Technical data
Accuracy class
Ambient temperature
°C
Protective class
Protection category: Housing/terminals
Approvals (according to type)
* Current transformer ratios / = 250 mA T
*
Current transformer ratios: 5:5, 50:5, 
100:5, 150:5, 200:5, 250:5, 300:5, 
400:5, 500:5, 600:5, 750:5, 1,000:5, 
1,250:5, 1,500:5.
** 0.01 kWh for readings ≤ 99,999.99 kWh
and 0.1 kWh for readings ≥ 100,000.0 kWh
*** 0.1 kWh for readings ≤ 999,999.9 kWh
and 1 kWh for readings ≥ 1,000,000 kWh
For outline drawing see page 8
R
T1,T2
= Tariff switching equipment
7E Series - Energy meter
7E.46.8.400.00x2
7E.56.8.400.00x0
X-2012, www
.finder
net.com