INSYS GSM 4.2 easy 
Function Descriptions 
January 07 
11
 
Function Descriptions 
3.1 
Definitions 
3.1.1  Objects, instances, object short names  
Programming of the Moeller easy takes place via objects. A digital input, a 
register, a counter for operating hours, a comparator, etc. are all examples for 
objects.  
Each object has an object short name. The digital register, for example, has the 
object short name "M", the analogue output has the short name "QA".  
Several instances of each object are available to the programmer. The easy 500 
device, for example, offers 16 digital registers “M”. The programmer can therefore 
select the object instances "M1" to "M16". 
3.1.2  Alias 
As not only the programmer of the compact controller is responsible for 
maintenance and operation of the Moeller easy device, it may not be clear for 
“outsiders” which object instance has which function. Therefore, so-called aliases 
were introduced for the INSYS GSM 4.2 easy. This offers the possibility to allocate 
a name that is easy to understand.  If the Moeller easy device controls a waste 
water system, for example, the digital register M1 can be allocated the alias 
"waste water pump1”. If an individual wants to activate the wastewater pump via 
mobile phone, using an SMS, he does not need to know that the register 1 must 
be used, but simply uses the term “wastewaterpump1”, Up to 30 object instances 
all in all can be allocated aliases. 
3.2 
Automatic Actions 
3.2.1  Object instances monitoring 
The values of the easy object instances are monitored to enable a fault message 
when values are changed. 
Monitoring is performed during polling operation, i.e. the INSYS GSM 4.2 easy will 
cyclically read out the easy object instances  and can thus detect any changes. Up 
to 10 object instances can be monitored altogether. 
The query interval can be set to seconds (1 to 255 seconds). These times represent 
minimum values. The actual monitoring interval may be slightly larger. If several 
values that need to be monitored have been configured, the communication with 
the compact controller may have a longer duration than the interval.