Insys GSM EASY 4.1 11-02-01-03-01.027 Benutzerhandbuch

Produktcode
11-02-01-03-01.027
Seite von 40
Function Descriptions 
INSYS GSM 4.2 easy 
14 
January 07
 
3.2.2 
Periodic SMS 
In addition to the monitoring of values, it is also possible to periodically query the 
current condition or value of an object instance and to send it automatically via 
SMS.  
A periodic SMS can be sent in hourly intervals of 1 to 255 h. After this time has 
expired, the set object instance is read out and the value is sent as SMS. 
The query of the object instance is performed up to three times, if necessary. If 
there is still no reply from the easy device, an SMS with the text "NO SUCCESS" is 
sent  instead of the object instance value. 
The sending of this SMS will be delayed, if one of the following functions is 
performed at this moment: 
¾
  Login state/field strength query (the LEDs STATUS and SIGNAL are updated); 
duration approximately 50 seconds, interval 60 seconds (may be switched off, 
but then the LEDs are no longer operated) 
¾
  Query of the SMS input buffer and processing of incoming SMS commands, if 
required; duration approximately 5 seconds plus processing time for 
command; interval 60 seconds (may be switched off, but then 
queries/configuration via SMS are no longer possible) 
¾
  GSM connections active (data connection, DTMF connection, security callback)   
¾
  Sending an SMS (fault message, Alive SMS may be switched off, Power up SMS 
may be switched off); duration approximately 10 seconds. 
 
If the LOGOUT time is active when the periodic SMS are processed, the module is 
logged in at the GSM network before sending, and logged out afterwards. 
Periodic SMS are only sent to one destination. The usage of further recipients is 
not possible. 
The text of a periodic SMS consists of an object short name, its instance, a “=”, and 
finally the value itself. If an alias was defined for periodically transmitted object 
instances, this alias is entered in the SMS text instead of the object short name 
and the instance. 
 Example: 
M12=1