MCS G2 Specifications
Dimensions
Height in U
42U
Maximum Height
78.9 in (2004 mm)
Maximum Width
35.8 in (909 mm)
Maximum Depth
51 in (1,270 mm)
Shipping Height (on skid)88.5 in (2248 mm)
Shipping Width (on skid)48 in (1220 mm)
Shipping Depth (on skid)70 in (1778 mm)
Ramp length
103 in (2616 mm)
Total length required for
offloading MCS G2
20.25 ft (6.17 m)
Weight
Net (including rack)
434 kg (957 1bs)
Shipping
1370 lbs (621.4 kg)
Load
Static
3000 lbs. (1364 kg)
Dynamic (CTO) weight
allowed
2000 lbs (908 kg)
Color
Graphite Metallic
Doors
Carbon
Frame
Hot Swap Components Heat exchangers
No
Fans
Yes
Cooling
Cooling agent
Primary or auxiliary chilled water supply
Condensate evacuation
tube
Yes
Air temperature regulation
Yes
Heat exchangers
1
Fans
6
Rack Front door
Transparent polycarbonate insert behind mesh
Rack Rear doors (split) Solid, no mesh
Chilled water connections
Rear
MCS G2 mounting
location
Left hand side
Side panels included
Yes
Max Cooling capacity 35kW
Air Temperature to servers
Settable, suggested at 68-77 ° F ( 20-25° C)
Air Flow to servers
2400 CFM Max
Recommended Chilled
Water inlet temperature
45.0 ° F ( 7.00 ° C) 7° to 15° C
Maximum Chilled Water
Flow Rate
15.8 US gallons per minute (60 liters per minute)
Chilled Water Pressure
Drop
17 psi (1.2 bar) at 60 liters per minute
QuickSpecs
HP Modular Cooling System G2
Technical Specifications
DA - 12919   Worldwide QuickSpecs — Version 5 — 10.9.2009