Beha Amprobe ACDC-400-D Digital-Multimeter, DMM, 3454596 Datenbogen

Produktcode
3454596
Seite von 98
5
SyMboLS
Battery
Refer to the manual
Double insulated
Dangerous Voltage
Direct Current
earth ground
Alternating Current
Audible tone
Conforms to relevant 
Australian standards.
Complies with eU directives
Do not dispose of this 
product as unsorted 
municipal waste.
Underwriters laboratories. 
[note: Canadian and US.]
Application around and 
removal from hazardous 
live conductors is permitted
SAfEty INfoRMAtIoN
The ACDC-400 Series Digital Clampmeters conform to en61010-1:2001; en61010- 
2-032:2002; CAT iii 600 V, class 2 and pollution deg.2
This instrument is en61010-1 certified for installation Category iii (600V). it is 
recommended for use in distribution level and fixed installations, as well as 
lesser installations, and not for primary supply lines, overhead lines and cable 
systems.
Do not exceed the maximum overload limits per function (see specifications) nor 
the limits marked on the instrument itself. never apply more than 600 Vdc/600 V 
ac rms between the test lead and earth ground.
 Warnings and Precautions
Before and after hazardous voltage measurements, test the voltage function on 
a known source such as line voltage to determine proper meter functioning.
Disconnect the test leads from the test points before changing meter functions.
Disconnected from the meter’s test leads before measuring current.
inspect the Clampmeter, test leads and accessories before every use. Do not use 
any damaged part.