Bender RCMA420-D-2 B74043002 Datenbogen
![Bender](https://files.manualsbrain.com/attachments/fa6278e11a0177b13bf7b5ed74490f730298e847/common/fit/150/50/35ae042b51251317c948d58cd92e82ba6c1c4a2c666876cf9e3c7f13d187/brand_logo.gif)
Produktcode
B74043002
TDB404006en / Main catalogue part 4 – Residual current monitors, Residual current monitoring systems / 07.2010
43
4.2
Residual current monitor RCMA420
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage
250 V
Rated impulse voltage/pollution degree
2.5 kV / III
Protective separation (reinforced insulation) between
(A1, A2) - (k, l, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage tests according to IEC 61010-1
2.21 kV
Supply voltage
RCMA420-D-1:
Supply voltage U
Supply voltage U
S
AC 16…72 V / DC 9.6…94 V
Frequency range U
S
42…460 Hz
RCMA420-D-2:
Supply voltage U
Supply voltage U
S
AC/DC 70…300 V
Frequency range U
S
42…460 Hz
Power consumption
≤ 3 VA
Measuring circuit
External measuring current transformer
W20AB, W35AB, W60AB series
Rated insulation voltage (measuring current transformer)
800 V
Operating characteristic acc. to IEC 62020 and IEC/TR 60755
Type B
Rated frequency
0…2000 Hz
Measuring range AC
0…1.5 A
Measuring range DC
0…600 mA
Relative uncertainty of the response value
0…-35%
Relative uncertainty
0…35%
Response values
Rated residual operating current I
Δn1
(prewarning, AL1)
50…100 % x I
Δn2
, (50 %)*
Rated residual operating current I
Δn2
(alarm, AL2)
10…500 mA (30 mA)*
Hysteresis
10…25 % (15 %)*
Specified time
Start-up delay t
0…10 s (0.5 s)*
Response delay t
on2
(alarm)
0…10 s (0 s)*
Response delay t
on1
(prewarning)
0…10 s (1 s)*
Delay on release t
off
0…99 s (1 s)*
Operating time t
ae
at I
Δn
= 1 x I
Δn1/2
≤ 180 ms
Operating time t
ae
at I
Δn
= 5 x I
Δn1/2
≤ 30 ms
Response time t
an
t
an
= t
ae
+ t
on1/2
Recovery time t
b
≤ 300 ms
Cable lengths for measuring current transformers
Connection (see ordering information)
connecting cable WX… 1 m / 2.5 m / 5 m / 10 m
Displays, memory
Display range, measured value AC
0…1.5 A
Display range, measured value DC
0…600 mA
Error of indication
± 17,5 % / ± 2 digit
Measured-value memory for alarm value
data record measured values
Password
off / 0…999 (off)*
Fault memory alarm relay
on / off (on)*
Inputs/outputs
Cable length for external test/reset button
0…10 m
Switching elements
Number of switching elements
2 x 1 changeover contact
Operating principle
N/C operation / N/O operation (N/C operation)*
Electrical endurance, number of cycles
10000
Contact data acc. to IEC 60947-5-1
Utilisation
Utilisation
category
AC-13 AC-14 DC-12 DC-12
DC-12
Rated operational voltage
230 V
230 V
24 V
110 V
220 V
Rated operational current
5 A
3 A
1 A
0.2 A
0.1 A
Minimum contact rating
1 mA at AC/DC ≥ 10 V
Environment/EMC
EMC
IEC 62020
Operating temperature
-25 ºC…+55 ºC
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3)
Stationary use (IEC 60721-3-3)
3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2)
2K3 (except condensation and formation of ice)
Long-time storage (IEC 60721-3-1)
1K4 (except condensation and formation of ice)
Classification of mechanical conditions IEC 60721
Stationary use (IEC 60721-3-3)
Stationary use (IEC 60721-3-3)
3M4
Transport (IEC 60721-3-2)
2M2
Long-time storage (IEC 60721-3-1)
1M3
Connection
Connection type
push-wire terminals
Connection properties
rigid
rigid
0.2…2.5 mm² / AWG 24-12
flexible without ferrule
0.2…2.5 mm² / AWG 24-12
flexible with ferrule
0.2…1.5 mm² / AWG 24-16
Stripping length
10 mm
Opening force
50 N
Test opening, diameter
2.1 mm
Other
Operating mode
continuous operation
Position of normal use
display-oriented
Degree of protection, internal components (IEC 60529)
IP30
Degree of protection, terminals (IEC 60529)
IP20
Enclosure material
polycarbonate
Flammability class
UL94V-0
DIN rail mounting acc. to
IEC 60715
Screw fixing
2 x M4 with mounting clip
Software version
D242 V1.1x
Operating manual
TGH1411
Weight
≤ 150 g
( )* = factory setting
Technical data