Bender RCMA420-D-2 B74043002 Datenbogen

Produktcode
B74043002
Seite von 4
 
 
TDB404006en / Main catalogue part 4 – Residual current monitors, Residual current monitoring systems / 07.2010 
43
4.2
Residual current monitor RCMA420
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage 
250 V
Rated impulse voltage/pollution degree 
2.5 kV / III
Protective separation (reinforced insulation) between
 
(A1, A2) - (k, l, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage tests according to IEC 61010-1 
2.21 kV
Supply voltage
RCMA420-D-1:
Supply voltage U
S
  
AC 16…72 V / DC 9.6…94 V
Frequency range U
S
  
42…460 Hz
RCMA420-D-2:
Supply voltage U
S
  
AC/DC 70…300 V
Frequency range U
S
  
42…460 Hz
Power consumption 
≤ 3 VA
Measuring circuit
External measuring current transformer  
W20AB, W35AB, W60AB series
Rated insulation voltage (measuring current transformer)  
800 V
Operating characteristic acc. to IEC 62020 and IEC/TR 60755  
Type B
Rated frequency  
0…2000 Hz
Measuring range AC  
0…1.5 A
Measuring range DC 
0…600 mA
Relative uncertainty of the response value 
0…-35%
Relative uncertainty  
0…35%
Response values
Rated residual operating current I
Δn1
 (prewarning, AL1)  
50…100 % x I
Δn2
, (50 %)*
Rated residual operating current I
Δn2
 (alarm, AL2)  
10…500 mA (30 mA)*
Hysteresis  
10…25 % (15 %)*
Specified time
Start-up delay t  
0…10 s (0.5 s)*
Response delay t
on2
 (alarm)  
0…10 s (0 s)*
Response delay t
on1
 (prewarning)  
0…10 s (1 s)*
Delay on release t
off
 
0…99 s (1 s)*
Operating time t
ae
 at I
Δn
 = 1 x I
Δn1/2
  
 ≤ 180 ms
Operating time t
ae
 at I
Δn
 = 5 x I
Δn1/2
  
 ≤ 30 ms
Response time t
an
  
 t
an
 = t
ae
 + t
on1/2
Recovery time t
b
  
 ≤ 300 ms
Cable lengths for measuring current transformers
Connection (see ordering information)  
 connecting cable WX… 1 m / 2.5 m / 5 m / 10 m
Displays, memory
Display range, measured value AC 
0…1.5 A
Display range, measured value DC  
0…600 mA
Error of indication  
± 17,5 % / ± 2 digit
Measured-value memory for alarm value  
data record measured values
Password  
off / 0…999 (off)*
Fault memory alarm relay  
on / off (on)*
Inputs/outputs
Cable length for external test/reset button 
0…10 m
Switching elements
Number of switching elements  
 2 x 1 changeover contact
Operating principle  
 N/C operation / N/O operation (N/C operation)*
Electrical endurance, number of cycles 
 10000
Contact data acc. to IEC 60947-5-1 
Utilisation 
category 
AC-13 AC-14 DC-12 DC-12  
DC-12
Rated operational voltage 
230 V 
230 V 
24 V 
110 V 
220 V
Rated operational current 
5 A  
3 A 
1 A 
0.2 A 
0.1 A
Minimum contact rating 
1 mA at AC/DC ≥ 10 V
Environment/EMC
EMC 
  IEC 62020
Operating temperature  
 -25 ºC…+55 ºC
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3) 
3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) 
2K3 (except condensation and formation of ice)
Long-time storage (IEC 60721-3-1) 
1K4 (except condensation and formation of ice)
Classification of mechanical conditions IEC 60721 
Stationary use (IEC 60721-3-3) 
3M4
Transport (IEC 60721-3-2) 
2M2
Long-time storage (IEC 60721-3-1) 
1M3
Connection
Connection type 
push-wire terminals
Connection properties
rigid 
0.2…2.5 mm² / AWG 24-12
flexible without ferrule 
0.2…2.5 mm² / AWG 24-12
flexible with ferrule 
0.2…1.5 mm² / AWG 24-16
Stripping length 
10 mm
Opening force 
50 N
Test opening, diameter 
2.1 mm
Other
Operating mode 
continuous operation
Position of normal use 
 display-oriented
Degree of protection, internal components (IEC 60529)  
 IP30
Degree of protection, terminals (IEC 60529) 
 IP20
Enclosure material 
 polycarbonate
Flammability class 
UL94V-0
DIN rail mounting acc. to 
 IEC 60715
Screw fixing 
 2 x M4 with mounting clip
Software version  
D242 V1.1x
Operating manual  
TGH1411
Weight  
≤ 150 g
( )* = factory setting
Technical data