Installation, connection and commissioning
20
4.3
Notes on mounting
The devices are suitable for the following types of installation:
 
Standard distribution panels according to DIN 43871 or DIN rail mount-
ing according to IEC 60715
 
Screw mounting using M4 screws
4.4
Block diagram
Fig. 4.1: Block diagram of a central NS protection with coupling switches
Danger of electric shock! 
Make sure that the installation area is disconnected
from any electrical source .
Consider the data on the rated voltage and supply
voltage
 as specified in the technical data! 
The length of the connecting cable of the device
connections DG1/2, D1, D2, DG3/4, D3, D4, RTG and
RT1 is to be limited to 3 m.
To ensure the VMD460-NA's functionality after a power
failure, it is recommended to use an external UPS.
G
Power generation system
Coupling switch
Coupling switch
VMD460
Public grid