Finder 72.01.9.024.0000 - 10A Level Control Monitoring Relay SPDT-CO 250Vac 72.01.9.024.0000 Datenbogen

Produktcode
72.01.9.024.0000
Seite von 12
10
72 Series - Monitoring relays
Electrode holder with two pole connector, one connected directly to the electrode and the second
connected to the grounded installation thread. Suitable for metal tank with G3/8” linkage.
Electrode not incuded. Order appropriate number of electrodes holders - additional to the relay. 072.51
Technical data
Max liquid temperature
°C + 100
Max tank pressure
bar 12
Cable grip
mm Ø 
≤ 6
Electrode material
stainless steel (AISI 316L)
072.51
Floor water sensor, designed for the detection and reporting of the presence of floor surface water.
072.11
Technical data
Electrode material
stainless steel (AISI 316L)
Wire capability of terminals
Max screw torque
Nm
0.8
Max. wire size
solid cable
stranded cable
mm
2
1 x 6 / 2 x 6
1 x 6 / 2 x 4
AWG
1 x 10 / 2 x 10 
1 x 10 / 2 x 12
Wire strip length
mm
9
Other data
Distance between electrodes and floor
mm
1
Floor fixing screw diameter
Maximum M5 
Maximum cable diameter
mm
10
Maximum length of cable connecting sensor to relay m
200 (with capacitance of 100 nF/km)
Max. liquid temperature
°C
+100
072.11
Floor surface water sensor for connection to electrode terminals
(B1 and B3) of 72.01 or 72.11 level control relay, set in
Emptying function (ES or E respectively).
For ice bank control in refrigeration systems it is suggested to use
the high sensitivity  (5...450kOhm) types - 72.01.8.024.0002 or
72.01.8.230.0002.
Function
Z1, Z2 only for types 72.11
Accessories for 72.01 and 72.11
IX-2012, www