When the Turn ON time interval comes to an end REV-201M turns OFF the load and REV-201M switches 
to the idle mode. LED color indicator changes to GREEN
1.2.3.3  Cyclic operation mode 
Figure 5 – Cyclic operation diagram
Each Channel work independently. Timing countdown on each channel starts from the moment of power 
supply application to the input terminals «L1-N» (Channel 1); «L2-N» (Channel 2).
 When the power supply is given to both or any of the channel then starts the timing countdown which is 
adjusted by the upper potentiometer knob T1 at this moment GREEN LED indicator glows and the power load 
is turned  OFF. After  the termination  of this time interval (T1) power  load  turns  ON  and starts  the timing 
countdown of another interval that is adjusted by lower potentiometer knob T2 and this is indicated with the 
RED LED indicator.
After  the termination  of the  T2  timing countdown  REV-201M  turns  OFF  the power   load and the  LED 
indicator changes to GREEN. From this moment new countdown basing the T1 timing starts and the process 
keep on working in cycle mode in this way further.
If you want to restart the cyclic process – you will have to turn  OFF  the power supply and turn it  ON 
afterwards.
1.2.3.4  Control Operation function
 
Figure 6 – Control Operation function diagram
ATTENTION! For the proper operation of REV-201M it should be connected in accordance with the 
parallel channels operation – Mode 2 (for details kindly see paragraph 1.1. Application).
After the power supply is given to the input terminals REV-201M turns ON the power load for the Channel 
1  –  simultaneously  RED  LED  (Channel   1)  and  GREEN  LED  (Channel   2)  indicator  starts  glowing  –  this 
indicates about the preliminary signalization with the fixed time delay of 10 seconds.
After this interval the output relay of the “Channel 1” turns OFF for the fixed time of 30 seconds – this is 
indicated by GREEN LED glowing on the “Channel 1”.
After the expiration of the pause for the “Channel 1”  GREEN  LED change the color to  RED  – second 
announcement signal with the time of 30 seconds;
After the end of the second announcement signal the output relay of the “Channel” 1  turns  OFF, LED 
changes from RED to GREEN and the output relay of the “Channel 2” turns ON. At the same time GREEN 
LED of the “Channel 2” change the color to RED and switches to IDLE state.
If you want to restart the algorithm – you will have to turn OFF the power supply and turn it ON afterwards. 
      ATTENTION!!!
-
In this mode of operation time adjustment knobs (T1 and T2) as well as the DIP switched for the 
time ranges (D1 and D2) doesn’t function. All timing frames and intervals are preprogrammed and 
NOVATEK- ELECTRO
                                                                                     REV-201М 
 
 
 
 “ ”
Position of DIP switches A
 
 
 
 “ ”
Position of DIP switches A
terminals
V
IDLE
terminal
s
terminals
V
s
s
s