UA964801 - User manual
User manual - UA964801
59
AN1 analogue imput
13
AI1
TC
14
For thermocouples K, S, R, J, T, E, N, B.
• Comply with polarity.
• For possible extensions, use a compensated wire
• Comply with polarity.
• For possible extensions, use a compensated wire
and terminals suitable for the thermocouples used
(compensated).
(compensated).
• When shielded cable is used, it should be grounded at one
side only.
13
AI1
14
PT/N
i100
Shield/Schermo
White/Bianco
Red/Rosso
Red/Rosso
15
For thermoresistances PT100, NI100.
• For the three-wire connection use wires with the same
• For the three-wire connection use wires with the same
section.
• For the two-wire connection short-circuit terminals 14 and
15.
• When shielded cable is used, it should be grounded at
one side only.
13
14
Rot/Red
Weiß/White
Rot/Red
15
14
AI1
15
PT
C/NT
C
Shield/Schermo
For thermoresistances NTC, PTC, PT500, PT1000 and
linear potentiometers.
When shielded cable is used, it should be grounded at
one side only to avoid ground loop currents.
When shielded cable is used, it should be grounded at
one side only to avoid ground loop currents.
13
V/I
+24Vdc
14
10
10
Shield/Schermo
For linear signals V / mA.
• Comply with polarity.
• When shielded cable is used, it should be grounded at one
side only.
• Comply with polarity.
• When shielded cable is used, it should be grounded at one
side only.
Example of connection for linear input Volt and mA
DRUCKTRANSMITTER/
PRESSURE TRANSMITTER
P :0...100mbar Pmax :3bar T :0..70°C
OUT
: 4...20mA
IN :9...33V DC
14
13
10
B
C
A
4..20mA
For linear signals 0/4 to 20 mA with three-wire sensor.
Comply with polarity:
A= Sensor output (+)
B= Sensor ground (-)
C= Sensor power supply (+24 Vdc / 35 mA)
Comply with polarity:
A= Sensor output (+)
B= Sensor ground (-)
C= Sensor power supply (+24 Vdc / 35 mA)
Externe Versorgung/
External supply
P :0...100mbar Pmax :3bar T :0..70°C
OUT
: 4...20mA
IN :9...33V DC
DRUCKTRANSMITTER/
PRESSURE TRANSMITTER
14
13
A
B
4...20mA
For linear signals 0/4 to 20 mA with external power of sensor.
Comply with polarity:
A= Sensor output (+)
B= Sensor ground (-)
Comply with polarity:
A= Sensor output (+)
B= Sensor ground (-)
P :0...100mbar Pmax :3bar T :0..70°C
OUT
: 4...20mA
IN :9...33V DC
10
14
C
A
DRUCKTRANSMITTER/
PRESSURE TRANSMITTER
4..20mA
For linear signals 0/4 to 20 mA with two-wire sensor.
Comply with polarity:
A= Sensor output
C= Sensor power supply (+24 Vdc / 35 mA)
Comply with polarity:
A= Sensor output
C= Sensor power supply (+24 Vdc / 35 mA)
Serial input
16
RS485
17
18
18
Schirm/Shield
RS485 Modbus RTU communication.
When shielded cable is used, it should be grounded at
one side only.
one side only.