UA964801 - User manual
User manual - UA964801
  67  
8.4 
Digital input functions
On the UA964801 model, digital inputs can be enabled by configuring the par. 95 
Digital input 1 and the par. 100 Digital Input 2.
•  Run: allows the action of relays and linear output.
• 
Hold: locks the conversion.
• 
Tare zero (AI): selects to zero the process value (tare function).
• 
Alarm reset: if one or more alarms are selected with manual reset and alarm 
conditions are no longer present, closing the digital input it is possible to 
restore the alarm output. 
• 
Totalizer reset: if the totalizer function is active, using the digital input it is 
possible to reset the counter. 
• 
Peaks reset: min. peak/max. peak/peak-to-peak values are reset. 
• 
Sum total: if the sum function is active, using the digital input it is possible to 
increase the “sum” counter as indicated by the process value. 
• 
Sum reset: if the sum function is active, using the digital input it is possible to 
reset the “sum” counter.
• 
Config. lock: if the digital input is active it is not possible to enter configuration 
or to modify the setpoints.
Selecting 
Digital input 1 or Digital input 2 on the alarm parameters, the related 
relays will activate togheter with the digital input; functions selected on 
parameters 95 and 100 will continue to work. 
8.5 
Peak values
The UA964801 is provided with a page 
for the visualization of peak values: max. 
peak, min. peak and peak-to-peak of 
analogue input. Keeping pressed 
Rst
 it 
is possible to reset the visualized values.
8.6 
Totalizer function
The totalizer function, which can be enable by par. 9 Totalizer, performs an instant 
measurement of the process and sums it  on a time basis to the previously totalized 
value.
On the dedicated page it is possible to 
see the instant process value and the 
totalized value: keeping pressed 
Rst
 it is 
possible to reset this value.
Ex.: if a sensor 4 to 20mA with F.s. 9000m
3
/hour is connected, it is necessary to 
select 
Hour on par. 9 
Totalizer.  The device will increase the totalized value 
considering the 
m
3
 flowing each second 
(2.5m
3
). 
8.7 
Sum function
The sum function, which can be enabled by par. 10 Sum function, allows to increase 
a counter adding the process value on command. It is an application typical for 
weighing systems
 
and allows to know the total weighed value. 
Press 
Sum Function
 to enter the 
function page. Pressing 
+
 the Process 
value is added to the counter. It is 
possible to reset the total value keeping 
pressed 
Rst
 and to fix “tare zero” of the 
process pressing 
Tar
.
Functions tare, sum and reset can be managed also by digital input if enabled on 
par. 95 Digital Input 1 and par. 100 Digital Input 2