Wachendorff UNIVERSALDISPLAY UA964801 24-230 V DC/AC UA964801 Datenbogen
Produktcode
UA964801
86
UA964801 - User manual
User manual - UA964801
87
62 Actuation delay
Alarm 1 delay.
-3600 to +3600 seconds. Default: 0
Negative: delay in alarm output phase.
Positive: delay in alarm entry phase.
Negative: delay in alarm output phase.
Positive: delay in alarm entry phase.
63 Lower limit
Lower limit for alarm 1 setpoint.
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors). Default: 0.
64 Upper limit
Upper limit for alarm 1 setpoint
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors). Default: 1000.
65 Protection
Alarm 1 set protection. Does not allow user to modify setpoint
Free
Free
Modification allowed (
Default)
Lock Protected
Hide
Hide
Protected and not visualized
11.4 Alarm 2
Parameters to configure the Alarm 2
69 Alarm type
Alarm 2 selection
Disabled (
Disabled (
Default)
Absolute alarm
Band alarm
Digital input 1
Digital input 2
L.B.A.
Remote control
Band alarm
Digital input 1
Digital input 2
L.B.A.
Remote control
70 Contact type
Selects the alarm 2 output contact and intervention type
Normally open (
Normally open (
Default)
Normally closed
N.O. - Dis pwr on
N.C. - Dis pwr on
N.O. - Dis pwr on
N.C. - Dis pwr on
71 Alarm threshold
Selects the alarm 2 setpoint
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors), Default: 0.0.
72 Deviation threshold
Selects the deviation from alarm 2 setpoint for the band alarm
0 to +32767 [Digit
2
] (degrees.tenths for temperature sensors), Default: 0.0.
73 Hysteresis
Alarm 2 hysteresis
-1000 to +1000 [Digit
2
] (degrees.tenths for temperature sensors), Default: 0.0.
74 Reset type
Alarm 2 contact reset type
Automatic
Automatic
(
Default)
Manual
Manual reset by keyboard
Manual stored Keeps relay status also after an eventual power failure
75 Error contact
State of contact for alarm 2 output in case of error
Open (
Open (
Default)
Closed