UA964801 - User manual
User manual - UA964801
93
11.8 Graphic
Parameters to configure the trend and bar graph management.
105 Graphic type
Selects the type of graph to be visualized on the relevant page.
Trend (
Trend (
Default)
Bar graph
106 Lower limit
Trend or bar graph lower limit.
-32767 to +32767 [Digit
-32767 to +32767 [Digit
2
], Default: 0.
107 Upper limit
Trend or bar graph upper limit.
-32767 to +32767 [Digit
-32767 to +32767 [Digit
2
], Default: 1000.
108 Trend time
Selects the trend sampling time.
1 to 3600 seconds,
1 to 3600 seconds,
Default: 60s.
109 Data logger
Enables the over time registration of the process in eeprom
The sampling time is equal to the trend upgrading time.
Disabled (
The sampling time is equal to the trend upgrading time.
Disabled (
Default)
Enabled
11.9 Analogue output in mA
Parameters to configure the analogue output in mA
112 Retransmission
Enables analogue output
Disabled (
Disabled (
Default)
Process
Alarm 1
Alarm 2
Remote control
Alarm 2
Remote control
113 Signal type
Selects the signal for the analogue output in mA
0 to 20 mA
4 to 20 mA (
0 to 20 mA
4 to 20 mA (
Default)
114 Lower limit
Analogue output mA lower limit range
-32767 to +32767 [Digit
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors), Default: 0
115 Upper limit
Analogue output mA upper limit range
-32767 to +32767 [Digit
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors) Default: 1000
116 Error value
Selects the value of the analogue output in mA in case of error
0 mA (
0 mA (
Default)
4 mA
20 mA
20 mA
11.10 Analogue output in Volt
Parameters to configure the analogue output in Volt
119 Retransmission
Enables analogue output
Disabled (
Disabled (
Default)
Process
Alarm 1
Alarm 2
Remote control
Alarm 1
Alarm 2
Remote control