LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
190
 
Manual, 06/2014, A5E33039675 
Functional description 
The function fetches the analog values from the inputs Ax and Ay.  
Ax and Ay are each multiplied by the value of the A (gain) parameter, and the value at 
parameter B (offset) is then added to the relevant product, i.e. 
(Ax • gain) + offset = actual value Ax or  
(Ay • gain) + offset = actual value Ay. 
The function forms the difference ("Δ") between the actual values Ax - Ay. 
Output Q is set or reset, depending on difference of the actual values Ax - Ay and the set 
thresholds. See the calculation rule below. 
Calculation rule 
●  If the On threshold ≥ Off threshold, then Q = if (actual value Ax - actual value Ay) > On or 
Q = 0 if (actual value Ax - actual value Ay) ≤ Off. 
●  If the On threshold < Off threshold, then Q = 1, if On ≤ (actual value Ax - actual value Ay) 
< Off. 
Setting the Par parameter 
The gain and offset parameters are used to adapt the sensors to the relevant application. 
View in programming mode: 
 
Example 
In a heating control system, the supply T
v
 and return line temperatures T
r
 are to be 
compared, for example with a sensor at AI2. 
A control signal is to be triggered (for example "heater On") when the difference between the 
supply and return line temperatures is greater than 15 °C. The control signal is reset when 
the difference is less than 5 °C. 
The process variable of the temperature is to be shown in parameter assignment mode. 
The thermocouples available have the following technical data: -30 °C to +70 °C, 0 VDC to 
10 VDC. 
 
Application 
Internal mapping 
-30 °C to 70 °C = 0 VDC to 10 VDC 
0 to 1000 
0 °C 
300 
→ Offset = -30