Wago 750-557 Fieldbus Independent I/O Module 750-557 Datenbogen
Produktcode
750-557
10 • 750-557 [4 AO DC ±10 V]
Process
Image
WAGO-I/O-SYSTEM
750
I/O
Modules
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
acc. to EN 50082-2 (96)
EMC-Emission of interference (CE)
acc. to EN 50081-1 (93)
EMC-Immunity to interference
(Ship building)
(Ship building)
acc. to Germanischer Lloyd (01)
EMC-Emission of interference
(Ship building)
(Ship building)
acc. to Germanischer Lloyd (01)
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
C
UL
US
(UL508)
ABS (American Bureau of Shipping)
BV (Bureau Veritas) (applied for)
GL (Germanischer Lloyd)
Cat. A, B, C, D
KR (Korean Register of Shipping)
LR (Lloyd's Register) (applied for)
Env. 1, 2, 3, 4
DNV (Det Norske Veritas)
Cl. B
NKK (Nippon Kaiji Kyokai)
C
UL
US
(UL1604)
Class I Div2 ABCD T4A
KEMA
II 3 G EEx nA II T4
Conformity Marking
More Information
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the Internet under:
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the Internet under:
System Description
2.1.1.6 Process
Image
The analog output module 750-557 transmits 16-bit data and 8 status bits per
channel.
channel.
The digitalized output value is transmitted in a data word (16 bits) as output
byte 0 (low) and output byte 1 (high) via the process image of the coupler /
controller.
This value is represented with a 12 bit resolution on bit B3 ... B14.
The three least significant bits (B0 ... B2) are not parsed.
byte 0 (low) and output byte 1 (high) via the process image of the coupler /
controller.
This value is represented with a 12 bit resolution on bit B3 ... B14.
The three least significant bits (B0 ... B2) are not parsed.