Wago 750-432 Fieldbus Independent I/O Module 750-432 Datenbogen

Produktcode
750-432
Seite von 1
750-432, 750-433 / 753-432, 753-433
Subject to design changes
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880 •D-32385 Minden Tel.:  +49(0)571/887-0
E-Mail: info@wago.com
25.04.2007
Hansastr. 27 •D-32423 Minden Fax: +49(0)571/887-169 www.wago.com
4-Channel Digital Input Module DC 24 V
2-conductor connection; high-side switching
Fig. Series 750 / Technical data see page 30 / Delivery without Mini WSB marker 
Series 750 / 753 marking see pages 20 ... 21 / 22 ... 23
DI 2 
Data contacts 
DI 4 
24 V 
DI 4 
DI 3 
DI 1 
DI 1 
DI 3 
24 V 
DI 2 
Power jumper contacts 
Status Status 
13  14 
+  + 
15  16 
13  14 

750-432 
+  + 
DI 2 
DI 1 
DI 3 
DI 
DI 4 
DI 
0 V 
24 V 
24 V 
24 V 
 10nF        
10 nF 
0 V 
750-432 

 

 

 

 
 
 
 
 
The digital input module receives control signals from digital field devices 
(sensors, etc.).
The module is a 4-input channel, 2-conductor device. Due to its four 24 V 
connections, four sensors may be directly connected to the module.
Each input module has a noise-rejection filter. This filter is available with 
different time constants.
An optocoupler is used for electrical isolation between the bus and the 
field side.
Description
Item no.
Pack. 
unit
4DI 24V DC 3.0ms/2-conductor
750-432
10 
1)
4DI 24V DC 0.2ms/2-conductor
750-433
10 
1)
4DI 24V DC 3.0ms/2-conductor 
(without connector)
753-432
10 
1)
4DI 24V DC 0.2ms/2-conductor 
(without connector)
753-433
10 
1)
1)
 Also available individually
Accessories
Item no.
Pack. 
unit
Connectors 
Connectors Series 753
753-110
25
Coding elements
753-150
100
Miniature WSB Quick marking system
plain
248-501
5
with marking
see pages 214 ... 215
Approvals
Series 750 and 753
r
 UL 508
Conformity marking
1
Series 750
Marine applications
see pages 24 ... 27
Technical Data
No. of inputs
4
Current consumpton (internal)
5.5 mA
Voltage via power jumper contacts
DC 24 V (-25 % ... +30 %)
Signal voltage (0)
DC -3 V ... +5 V
Signal voltage (1)
DC 15 V ... 30 V
Input filter
3.0 ms (750-432 / 753-432)
0.2 ms (750-433 / 753-433)
Input current typ.
4.5 mA
Isolation
500 V system / supply
Internal bit width
4 bits in
Wire connection
CAGE CLAMP
®
Cross sections
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped length series 750 / 753
8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in
Width
12 mm
Weight
approx. 50 g
EMC 1-Immunity to interference
acc. to EN 50082-2 (1996)
EMC 1-Emission of interference
acc. to EN 50081-1 (1993)
EMC marine applications - 
Immunity to interference
acc. to Germanischer Lloyd (2001)
EMC marine applications - 
Emission of interference
acc. to Germanischer Lloyd (2001)