Wago 750-333 PROFIBUS DP/V1 FIELD BUSCOUPLER 12 MBaud 750-333 Datenbogen

Produktcode
750-333
Seite von 154
Fieldbus coupler / controller
•  97
Fieldbus Controller 750-833
WAGO-I/O-SYSTEM 750
D R A F T
PROFIBUS
2001-02-27
3.2.8 
Configuration and parameterisation of I/O modules
3.2.8.1 
Digital I/O modules
All binary I/O modules contain 3 bytes of extended parameterisation informa-
tion, which serve, amongst others, for the identification of the internal bus and
the structure of the mapping table. For modules capable of diagnosis the diag-
nosis message can be suppressed or released channel for channel or module for
module. Binary outputs offer the possibility to switch parameterisable substi-
tute values in the case of a master failure.
Note
For simplification only the article numbers are shown as module designation
in the table. The module „750-400“ thus corresponds to the module „750-400
2 DI/24 V DC/3.0 ms“
3.2.8.1.1 
2 DI I/O modules
Module
Identification
hex
Identification
dec
750-400, 750-401, 750-405, 750-406, 750-410,
750-411, 750-412
0x10
16
*750-400, *750-401, *750-405, *750-406, *750-410,
 *750-411, *750-412
0x00
0
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is:
plug fitted*)
- supplied by the I/O module
not plug fitted
- set to zero by the controller
*) 
Default setting
Parameter
Offset
Information
0
7
6
5
4
3
2
1
0
0
PFC
Plug
0
0
0
0
0
1
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
1
2
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
PFC
6
0
1
Module is mapped in the fieldbus and PFC-PI
Module is exclusively mapped in the PFC-PI
Plug
5
0
1
Module is physically not present
Module is physically present (default)
Italic
Cannot be changed