Wago 750-333 PROFIBUS DP/V1 FIELD BUSCOUPLER 12 MBaud 750-333 Datenbogen

Produktcode
750-333
Seite von 154
114  • Fieldbus coupler / controller
Fieldbus Controller 750-833
D R A F T
WAGO-I/O-SYSTEM 750
2001-02-27
PROFIBUS
3.2.8.5 Serial 
interfaces
All serial interface modules have 2 bytes of extended parameter information
which serves for the identification on the internal bus and the structure of the
mapping table. 2 further bytes follow which are reserved for future options.
Module
Identification
hex
Identification
dec
750-650, 750-651, 750-653, 750-654 (3 Byte)
0xB3
179
750-650, 750-651, 750-653, 750-654 (5 Byte)
0xB5
181
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is:
plug fitted*)
- supplied by the I/O module or
   supplied to the I/O module
not plug fitted
- set to zero by the controller or
   ignored by the controller
Diagnosis channel x
The diagnosis information of the corresponding
channel is
released
- transmitted to PROFIBUS-DP master
locked
*)
- not transmitted to PROFIBUS-DP master
*) 
Default setting
Parameter
Offset
Information
0
7
6
5
4
3
2
1
0
0
PFC
Plug
0
0
Diag
En0
0
0
1
7
6
5
4
3
2
1
0
reserved
2
15
14
13
12
11
10
9
8
reserved
3
7
6
5
4
3
2
1
0
reserved
PFC
6
0
1
Module is mapped in the fieldbus and PFC-PI
Module is exclusively mapped in the PFC-PI
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
0
1
Diagnosis locked (default)
Diagnosis release
Italic
Cannot be changed