Fieldbus coupler / controller •  127
Fieldbus Controller 750-833
WAGO-I/O-SYSTEM 750
D R A F T
PROFIBUS
2001-02-27
3.2.11.4 Node 
status
The 'I/O' LED indicates the node operation and signals the occurrence of a
fault.
I/O
USR
Meaning
green
*
Data cycle on the internal bus
off
*
No data cycle on the internal bus
red
on
Bus controller is in bootstrap mode or hardware defect on the controller
systems
red
blinks
*
During start up: internal bus being initialised
During operation: general internal bus fault
red
blinks
*
Fault message during internal bus reset and internal fault
orange
*
FLASH access to bus device firmware
* Not relevant
The controller starts up after switching on the supply voltage. The "I/O" LED
blinks. The "I/O" LED has a steady light following a fault free run-up.
In the case of a fault the "I/O" LED continues blinking. The fault is cyclically
displayed by the blink code.
“I/O”-LED an
Versorgungsspannung
einschalten
Koppler-Hochlauf
“I/O”-LED blinkt
Feldbusstart
Ja
Fehler
Nein
“I/O”-LED
1. Blinksequenz
(leitet opt. Anzeige eines Fehlers ein)
1. Pause
“I/O”-LED
2. Blinksequenz
Fehlercode
(Anzahl Blinkimpulse)
2. Pause
“I/O”-LED
3. Blinksequenz
Fehlerargument
(Anz. Blinkimp.)
Fig. 3-23: Signalling the LED node status
g012111d
After overcoming a fault restart the controller by switching off the supply volt-
age and then on again.