Explosive Environments •  137
Classification meeting CENELEC / IEC
WAGO-I/O-SYSTEM 750
D R A F T
PROFIBUS
2001-02-27
Explosive areas resulting from combustible gases, fumes or mist:
•  Zone 0 areas are subject to an explosive atmosphere
(> 1000 h /year) continuously or for extended periods.
•  Zone 1 areas can expect the occasional occurrence of an explosive atmos-
phere (> 10 h 
≤ 1000 h /year).
•  Zone 2 areas can expect the rare or short-term occurrence of an explosive
atmosphere (> 0 h 
≤ 10 h /year).
Explosive areas subject to air-borne dust:
•  Zone 20 areas are subject to an explosive atmosphere
(> 1000 h /year) continuously or for extended periods.
•  Zone 21 areas can expect the occasional occurrence of an explosive atmos-
phere (> 10 h 
≤ 1000 h /year).
•  Zone 22 areas can expect the rare or short-term occurrence of an explosive
atmosphere (> 0 h 
≤ 10 h /year).
7.3.2 
Explosion protection group
In addition, the electrical components for explosive areas are subdivided into
two groups:
Group I:
Group I includes electrical components for use in fire-damp
mine structures.
Group II:
Group II includes electrical components for use in all other
explosive environments. The group is further subdivided by
pertinent combustible gasesin the environment.
Subdivision  IIA, IIB and IIC takes into account that differ-
ent materials/substances/gases have various ignition energy
characteristic values. For this reason the three sub-groups
are assigned representative types of gases:
•  IIA – Propane
•  IIB – Ethylene
•  IIC – Hydrogen
Minimal ignition energy of representative types of gases
Explosion group
I
IIA
IIB
IIC
Gases
Methane
Propane
Ethylene
Hydrogen
Ignition energy (mWs) 0,28
0,25
0,082
0,016