Fieldbus coupler / controller
Fieldbus coupler 750-333
D R A F T
WAGO-I/O-SYSTEM 750
2001-02-27
PROFIBUS
3.1.8.2.3 
2 AO I/O modules
All analog modules have 6 bytes of extended parameterisation information and
offer the possibility of switching in parameterisable substitute values in the
case of a master failure.
Module
Identification
hex
Identification
dec
750-550, 750-552, 750-554, 750-556
0x61
97
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is:
plug fitted*)
- supplied by the I/O module
not plug fitted
- ignored by the coupler
Diagnosis channel x
The diagnosis information of the corresponding
channel is
released
- transmitted to PROFIBUS-DP master
locked
*)
- not transmitted to PROFIBUS-DP master
Substitute value channel x
0x0000 or 0x8000
0 or -32767
...  0x7FFF
...  32767
If, in the case of a PROFIBUS-DP fault, the
switching of substitute values is enabled by the
bus coupler parameterisation, this data is trans-
mitted to the periphery in the case of a fault.
*) 
Default settings
Parameter
Offset
Information
0
7
6
5
4
3
2
1
0
0
0
Plug
0
0
0
0
0
1
7
6
5
4
3
2
1
0
reserved
2
15
14
13
12
11
9
8
7
SubVal_Ch1_HB
3
7
6
5
4
3
2
1
0
SubVal_Ch1_LB
4
15
14
13
12
11
10
9
8
SubVal_Ch2_HB
5
7
6
5
4
3
2
1
0
SubVal_Ch2_LB
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SubVal_Ch1
0x0000
:
0xFFFF
Substitute value channel 1
SubVal_Ch2
0x0000
:
0xFFFF
Substitute value channel  2
Italic
Cannot be changed