Fieldbus coupler / controller
Fieldbus coupler 750-333
D R A F T
WAGO-I/O-SYSTEM 750
2001-02-27
PROFIBUS
3.1.9.1 
Station status 1 to 3
see EN 50170
3.1.9.2 
PROFIBUS-DP master address
The PROFIBUS-DP master address is located in byte 3 of the slave diagnosis
and includes the address of the master which has parameterised the station and
which has read and write access.
3.1.9.3 Manufacturer‘s 
identification
The manufacturer’s identification is located in byte 4 and 5 and includes a 16
bit code, which serves for the identification of the device or the device class.
3.1.9.4 
Identification based diagnosis
The identification based diagnosis comprises of a bit field, which contains one
bit of information for each connected module. The individual bit provides evi-
dence about the current operating status. A 0 means no fault, a 1 indicates a
faulty module condition. The bus coupler can be equipped with up to 63 mod-
ules, so that the identification based diagnosis including the header covers 9
bytes from byte 6 to byte 14.
Byte
Information
Meaning
6
0
1
0
0
1
0
0
1
Header  byte
(9 byte identification based diagnosis
incl. header)
7
7
6
5
4
3
2
1
0
8
15 14 13 12 11 10 9
8
9
23 22 21 20 19 18 17 16 Diagnosis allocation to
10
31 30 29 28 27 26 25 24 I/O module n (n=1 ... 63)
11
39 38 37 36 35 34 33 32 Coupler (n=0)
12
47 46 45 44 43 42 41 40
13
55 54 53 52 51 50 49 48
14
63 62 61 60 59 58 57 56