Fault message via the blink code of the I/O LED
Fault argument
Fault description
Fault code 1: Hardware and configuration fault
0
EEPROM check sum fault / check sum fault in parameter area of the
flash memory
flash memory
1
Overflow of the internal buffer memory for the inline code
2
Unknown data type
3
Module type of the flash program memory could not be determined /
is incorrect
is incorrect
4
Fault during writing in the flash memory
5
Fault when deleting the FLASH memory
6
Changed I/O module configuration found after AUTORESET
7
Fault when writing in the serial EEPROM
8
Invalid firmware
Fault code 2: Fault in programmed configuration
0
Incorrect table entry
Fault code 3: Internal bus command fault
0
I/O module(s) has (have) identified internal bus command as incor-
rect
rect
Fault code 4: Internal bus data fault
0
Data fault on internal bus or
Internal bus interruption on coupler
Internal bus interruption on coupler
n* (n>0)
Internal bus interrupted after I/O module n
Fault code 5: Register communication fault
n*
Internal bus fault during register communication with the I/O module
n
n
Fault code 7: I/O module not supported
n*
I/O module not supported at position n
* The number of blink pulses (n) indicates the position of the I/O module. I/O modules
without data are not counted (e.g. supply module without diagnosis)
without data are not counted (e.g. supply module without diagnosis)
Example: the 13
th
I/O module is removed.
1.
The "I/O" LED generates a fault display with the first blink sequence (approx. 10 Hz).
2.
The first pause is followed by the second blink sequence (approx. 1 Hz). The "I/O"
LED blinks four times and thus signals the fault code 4 (internal bus data fault).
LED blinks four times and thus signals the fault code 4 (internal bus data fault).
3.
The third blink sequence follows the second pause. The "I/O ERR" LED blinks twelve
times. The fault argument 12 means that the internal bus is interrupted after the 12
times. The fault argument 12 means that the internal bus is interrupted after the 12
th
I/O module.