WAGO-I/O-SYSTEM 750
2001-02-27
PROFIBUS
3.2.6 
Parameterisation of the controllers
Before a data exchange can be performed between master and slave, a param-
eterisation is required in addition to configuration.
The extended parameters (Extended User_Prm_Data) are provided via the
GSD files as selectable text in the configuration programs.
Description
Value
Meaning
Restart the internal bus after a
fault
Restart of the terminal bus following a fault,
such as, for example, no termination module
POWER ON RESET
*)
following an interruption of the supply
AUTORESET
immediately after overcoming the internal bus
fault
I/O module diagnosis
The diagnosis information of all I/O modules
with a diagnosis capability, for which the
diagnosis is released are
released
*)
transferred to PROFIBUS-DP master,
locked
not transferred to PROFIBUS-DP master
Process value display
Word or double word oriented process data, is
transferred to PROFIBUS-DP master in:
INTEL
„Little Endian Format“
MOTOROLA
*)
„Big Endian Format“
Behaviour in case of a
PROFIBUS DP fault
In the case of a malfunction of the
PROFIBUS DP communication the status of the
connected output periphery can be influenced in
various ways:
Stop internal bus transmis-
sion
The process data exchange on the internal bus is
stopped, all outputs drop out after a module
specific monitoring time of  100 ms
Set output image to zero
all outputs are immediately reset
Freeze output image
all outputs maintain the last status before the
malfunction
Write substitute value
*)
all outputs switch a parameterisable substitute
value
PFC fault strategy
PFC takes over the control via the output image
Reaction to an internal bus fault
In the event of a malfunction of an internal
communication between fieldbus controller and
I/O modules, such as, for example no termina-
tion module,
Stop PROFIBUS data
exchange
*)
the data exchange with the PROFIBUS master
is stopped.
Set input image to zero
the input information is set to zero
Freeze input image
the input information prevailing before the fault
is maintained
*) 
Default settings