Lappkabel UNITRONIC® Bus cable EIB 2 x 2 x 0.8 mm² Green 2170240 Datenbogen

Produktcode
2170240
Seite von 1
DATA SHEET 
2170240 
 
UNITRONIC
®
 BUS EIB 
gültig ab : 
13.10.2009
 
 
elaborated by:  
Petra Samek,  PDC       
Dokument: 
DB2170240DE05 
Blatt 1 von 1 
 
Nr.: 0019/0408 
Application 
Screened installation cable based on type J-Y(ST)Y in acc. to VDE 0815 for data transmission in the building 
management, in particular as bus cable for the European Installation Bus “EIB” (use for decentralised control of 
lighting, heating, air-conditioning, ventilation, energy management, blind, time management, locking systems 
etc.). The EIB bus cable can be laid in, on and under plaster, in pipes and cable ducts, in dry, damp and wet 
rooms. They may only be installed outdoors with UV-protection and in observation of the temperature range. 
UNITRONIC
®
 BUS EIB cables have been tested with a test voltage of 4 kV. The cables may be laid respectively 
be touched without restrictions next to power cables. 
Design 
Conductor 
Solid, bare copper wire, Ø 0.8 mm diameter 
Insulation 
special PVC-based compound 
Core identification  pair 1: red and black, pair 2: white and yellow 
Stranding 
4 insulated conductors twisted (star-quad formation) 
Wrapping 
plastic foil 
Screening 
one layer plastics-coated aluminium foil, wrap metal side inside with Ø 0.4 mm 
bare copper drain wire 
Sheath 
special PVC-based compound, Ø max. 6.6 mm 
Sheath colour 
green, similar to RAL 6017  
Electrical properties at 20°C 
Conductor resistance 
max. Ω/km
73.2 
Insulation resistance 
min. MΩ x km
100 
Mutual capacitance at 800 Hz 
nom. nF/km
100 
Inductance at 800 Hz 
mH/km
0.65 
Capacitive coupling k at 800 Hz 
max. pF/100 m
300 
Characteristic impedance at 100 kHz 
nom. Ω
85 
Characteristic impedance at 1MHz 
nom. Ω
75 
Attenuation at 10 kHz 
nom. dB/km
3.5 
Attenuation at 100 kHz 
nom. dB/km
Operating voltage (not for power purposes) 
peak value  V
300 
Test voltage (conductor/conductor) 
V
1000 
Test voltage (conductor/screen) 
V
1000 
Test voltage of the cable in water bath (5 min.) 
V
4000 
Mechanical and thermal properties 
Minimum bending radius (fixed use) 
cableØ  
x 10 
Permissible pulling strength 
max. N
100 
Permissible temperature range (fixed use) 
°C
-30 to +70 
Flame propagation 
flame retardant acc. to IEC 60332-1-2
Conformity 
This cable confirms to RoHS directive (2002/95/EG)