Lappkabel UNITRONIC® AS-INTERFACE 2 x 1.5 YE Yellow 2170830 Datenbogen

Produktcode
2170830
Seite von 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
 
 
UNITRONIC
®
 BUS ASI FD (TPE) A
 
 
DB 2170830                      
valid from: 02.02.2010
 
 
 
Originator: P. Samek / PDC
 
approved: H. Pfeffer / PDC 
Document: 
DB2170830EN 
page 1 of 1 
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.  
PD 0019/2.1_11.09EN 
APPLICATION 
 
UNITRONIC
 BUS ASI FD (TPE) A is a field-bus cable with two cores for AS-INTERFACE (Actuator-Sensor Interface). 
Networking system for the lower field area. 
Data transmission for AS-Interface telegrams and power supply for AS-Interface slaves, master, repeater, extender and 
sensors is done via this unscreened, geometrically-coded two-core flat cable. Contacting the conductors without stripping 
the insulation by insulation-displacement-system of AS-I modules. 
The oil-resistant outer sheath of this field-bus cable recommends its use in typical industrial environment, especially in wet 
areas of automotive industry, machining centres, especially in combination with water-based and water-mixable cooling 
lubricants. 
The cable is intended for flexible application and permanent installation in interiors by low and high temperatures.  
The cable can be used in power chains. 
 
Approvals:  
UL AWM   Style 2103 
 
 
CSA  AWM II A/B 105°C  300V  FT1 
 
 
DESIGN 
 
 
 
Conductor 
 
tinned copper wires, 1.5 mm², finest wires in acc.  to VDE 0295 class 6 
Insulation 
 
TPE, oil resistant 
 
 
 
Coding: brown and blue 
Lay 
 
 
two cores flat parallel. The brown core is on the side of the „nose“ 
 
 
 
The cores must be powdered with talc and the cores must not stick together with the sheath  
Sheath   
 
TPE, oil resistant, flame retardant 
 
 
 
Sheath colour yellow, RAL 1012   Part no. 2170830 
printing ink: black 
 
 
 
Sheath colour black, RAL 9005  
Part no. 2170831 
printing ink: white 
 
 
TECHNICAL DATA 
 
Conductor resistance acc. to VDE 0295 
≤ 13.7 Ω/km 
Specific insulation resistance 
≥ 1 M Ω x km 
Capacitance at 1 kHz 
≤ 80 nF/km 
Inductance 
0.5 … 0.75 mH/km 
Characteristic impedance 167 kHz 
70 … 140 Ω 
Operating Voltage  
∼ 30 V 
Operating Peak Voltage  
(not for power purposes) 
300 V 
Test voltage 
2 kV 
 
 
Temperature range, static 
- 40 to + 105°C 
Temperature range, for flexible use 
- 30 to + 105°C 
Minimum bending radius, static 
12 mm 
Minimum bending radius, for flexible use 
60 mm 
 
 
Flame propagation 
flame retardant in acc. to IEC 60 332-1-2 
 
/ UL 1581 Sec. 1100 (FT-2 flame test) and Sec. 1060 (FT-1) 
Oil resistance and cutting oil resistance 
acc. to UL 758 Sec. 15 (60°C)  
 
 
GENERAL REQUIREMENTS 
 
RoHS:     This cable is conform to RoHS directive (2002/95/EG)