Lappkabel 2170234 UNITRONIC BUS PA 1 x 2 x 1 BK Blue 2170234 Datenbogen

Produktcode
2170234
Seite von 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
    
 
UNITRONIC BUS PA 1 x 2 x 1,0
 
 
DB2170234                   
valid from: 03.07.2012 
 
Originator: RAWE/PDC 
approved: HAPF/PDC
 
Document: 
DB2170234 
page 1 of 1 
All rights reserved acc. to DIN ISO 16016. 
PD 0019/2.2_11.10DE 
Application  
Data cable for PROFIBUS PA field net according to IEC 61158-2.  
The cable is intended for fixes laying in dry and damp interiors and with the black outer sheath for laying outdoors. 
Design 
Conductor  
bare copper, nom. 1,0 mm
2
, ca. 1.32 mm ∅, fine-wire stranded 
Insulation 
foam-skin PE, core  nom. 2,5 mm 
Core identification code 
cores red and green 
Stranding 
2 cores together with two fillers  
Wrapping 
1 layer PETP plastic foil 
Screening 
braid of tinned copper wires, coverage 85 % (nominal value)  
Outer sheath 
PVC lead-free, blue similar to RAL 5015 or black similar to RAL 9005,  
wall thickness nom. 1,0 mm, outer diameter: 8,0 mm  
Electrical properties at 20° C 
Resistance (loop)  
max. 44 Ω/km 
Insulation resistance 
min. 5 GΩxkm 
Mutual capacitance 
A/A: ca. 50 nF/km 
A/S: ca. 80 nF/km 
(at 800 Hz) 
Inductance 
800 Hz: ca. 0,4 mH/km 
Characteristic impedance 
31,25 kHz: 100 Ω ± 20% 
   ≥ 1 MHz: nom. 80 Ω 
Line attenuation 
  39 kHz: max. 0,3 dB/100 m 
100 kHz: nom. 0,35 dB/100 m 
   1 MHz: nom. 1,2 dB/100 m 
Velocity of propagation 
nom. 79% 
Transfer impedance up to 30 MHz 
max. 250 mΩ/m 
Operating peak voltage 
250 V (not for power purposes) 
Test voltage U
eff.
 core/core and  
core/screen  
1500 V 
Mechanical and thermal properties 
Minimum bending radius 
static: 65 mm 
Permissible temperature range 
during installation:   -5˚ C up to +60˚ C 
                    static: -40˚ C up to +80˚ C 
Flame propagation 
flame retardant acc. to IEC 60332-1-2 
General requirements 
Dangerous and forbidden substances acc. to RoHS directive (2002/95/EG) are 
not allowed to the manufacturing.