Fanox D30/230V AC D30/230V AC D30/230V AC Datenbogen

Produktcode
D30/230V AC
Seite von 1
25
CT-1
CTD-1
• Electronic relays with adjustable delay time and sensitivity.
• Suitable for direct pulse current.
• Practically immune to external disturbances.
Relay with adjustable delay time
and sensitivity / Multirange relay
Multirange relay. 22,5 mm wide
Toroidal transformers
• To be used with CT-1 transformers.
• Modular size. DIN rail mounting .
• Sealable front cover.
• Very high level of inmunity.
• 22,5 mm wide. Saving space in the distribution
board.
• DIN rail mounting.
• To be used with CT-1 transformers.
• Suitable for Motor Control Centres (MCC) and
electrical distribution board in general.
• To be used with ELR-B, ELR-3C and D30 relays.
• The transformer and relay assembly sensitivity is
fixed by the relay.
• The toroidal transformer CTD-1/28 is specifically
designed for DIN rail mountig.
Working principles: The toroidal transformer is
installed between the source and the load. The
system works on the current balance principle. In
a correct installation the vector sum of the
currents is zero and the relay will not trip.
In case of an insulation fault on the circuit a
leakage current flows to earth. Now the vector
sum of the current passing through the
transformer is not zero, this inbalance is
detected by the transformer, which induces a
current in the secondary winding which is
connected to the relay.
If the fault level is higher than the selected
sensitivity, and when the trip time delay has
elapsed, the relay trips and actuates on the shunt
trip of a circuit breaker or the coil of a contactor
interrupting the supply to the load.
The dimensioning of the toroidal transformer
depends on the diameter of all active wires   (not
earth conductors) put through the
transformers.
In combination with CT-1
20 m with cables twisted 
Automatic, manual and remote (in manual mode
disconnect the aux. supply during 1s)
2 LED's: ON + Trip
Normally de-energized 
1 change over NO-NC
5A - 250V
2,5 mm
2
3 VA
3 modules x 17,5 mm = 52,5 mm
50/60 Hz
IP-20 / 0,2 kg
-10°C +60°C
IEC 41-1, IEC 255, VDE 0664, EN 50081-1, EN 50082-2
D30
Adjustable from 0,03 A to 30 A
Adjustable from 0,02 s to 5 s
120 Vac
230 Vac
41021
41020 
Type
Inner Ø 
Code no. Weight (kg)
CTD-1/28
28 mm
41055
0,2
CT-1/35
35 mm
41025
0,2
CT-1/60
60 mm
41030
0,3
CT-1/80
80 mm
41035
0,5
CT-1/110
110 mm
41040
0,5
CT-1/160
160 mm
41045
1,4
CT-1/210
210 mm
41050
1,5
ELR-B            ELR-3C
D 30
ELR-B ELR-3C
0,3 A or 0,5 A
Adjustable from 0,025 A to 25 A
0,02 s or 0,5 s
Adjustable from 0,02 s to 5 s
24-48 Vdc, ac
115 Vdc, ac
24-48 Vdc, ac
115 Vdc, ac
230-400 Vac
230-400 Vac
41012
41010
41005
41000
In combination with CT-1
20 m with cables twisted 
Automatic, manual and remote (in manual mode
disconnect the aux. supply during 1s)
2 LED's: ON +    (Trip)
Selectable: normally de-energized (N) / or energized (P)
1 change over NO-NC
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
2,5 mm
2
7 VA - 230V
No. 22,5 mm wide
50/60 Hz
IP-20 / 0,2 kg
-10°C +60°C
EN 60947-2-B,EN 50263,EN61543 (A11), IEC60255-5, VDE 0664
14 12 10
7 5
3 1
16
16
1
2
17
18
Load
Earth
N R S T
Ba
U
s
V
CT-1
7-1 = 380-415 Vac
7-3 = 220-240 Vac
7-5 = 110-127 Vac-dc
7-3 = 48 Vac-dc
7-5 = 24 Vac-dc
U
s
Ba = shunt trip
14 10 12
A1
1
2
Load
Earth
N R S T
Ba
U
s
V
CT-1
Ba = shunt trip
1
2
A2
Connecting diagram for output relay normally
de-energized (N).
For output relay normally energized (P) connect
Ba to 12-14 terminals
ingles interior 2008:ingles interior 2005  13/5/08  15:33  Página 25