Secuself Wireless gas detector EL-2762 / E8US036GAS0A EL-2762 / E8US036GAS0A Datenbogen

Produktcode
EL-2762 / E8US036GAS0A
Seite von 2
Page 
1
 
 
Wireless Gas Leak Detector 
(Model EL-2762) 
Introduction 
Electronics Line Ltd's Wireless Gas Leak Detector detects 
mixtures of air and combustible gases (Natural Gas, Methane, 
Propane and Butane). 
Upon detecting the presence of gas, the unit emits an alarm and 
notifies the control panel. 
The main features of your Wireless Gas Leak Detector include the 
following: 
  Integrated transmitter designed for use EL's wireless alarm 
systems 
  Easy to install 
  Monitoring for Natural Gas, Methane, Propane and Butane in 
a continuous manner 
  Loud alarm (85 dB) when detecting a buildup of Gas   
  Test button   
  Self-test 
Selecting the installation location 
The Wireless Gas Leak Detector will function effectively if installed in the 
correct location. Consider the following before mounting the gas alarm:   
  Methane (Natural) Gas: Methane is lighter than air, 
therefore the greatest concentration of gas is found right 
below the ceiling, and therefore the Wireless Gas Leak 
Detector should be installed on the wall, approximately 30 
cm (12”)
 below the ceiling.   
  Butane Gas: Propane and Butane are heavier than air, 
therefore the greatest concentration of gas is found right 
above the floor level. The Wireless Gas Leak Detector 
should therefore be installed about 30cm (12
”) above the 
floor. Do not mount in a location where the gas alarm 
could be damaged by dirt, liquids, etc. 
Note:   
Do not install the detector on the ceiling or on the floor.   
Floor
Ceiling
30 cm (12")
30 cm (12")
Detector location for Methane (Natural) Gas detection
Detector location for Propane and Butane detection
 
  Install the 
detector 
in close proximity to every 
gas-operated appliance.   
Do not:   
  Install the gas detector directly on any gas appliance.     
  Install the gas detector in sealed or closed compartments or 
in an area where a wall or a closed door can obstructs the 
flow of gas to the gas alarm.     
  Install the gas detector in locations where fans, open doors, 
open windows etc. may prevent gas from reaching the 
sensor.   
  Install the gas 
detector 
in any room where aerosols or 
ammonia are used (e.g. bathrooms).   
To install the detector: 
1.  Remove the mounting bracket from your unit according to Fig. 1. 
1
2
3
 
Fig. 1 
2.  Hold the Mounting bracket against the wall as a template and 
mark the locations for the 2 mounting holes.   
3.  Using a 3/16-inch (5 mm) drill bit, drill two holes at the marks 
and insert wall plugs (Fig. 2)
 
Fig. 2
 
4.  Secure the mounting bracket to the wall. 
5.  Line up the side slot of the bracket and the detector. Push the 
detector onto the mounting bracket and fix it (see arrow 
direction, Fig. 2). Pull the detector outwards to make sure that it 
is securely attached to the mounting bracket. 
6.  Connect the detector power cable to the wall power outlet. 
Transmitter/Receiver Communication Setup   
1. 
Set the panel to registration mode. 
2. 
Insert the batteries into compartment. The detector enters 
registration mode during which a transmission is sent every 
few seconds. You can terminate registration mode by 
pressing the Test Button. Test mode is automatically 
terminated after approximately five minutes. 
3. 
Verify that the detector has been identified by the receiver. 
TEST/HUSH
POWER
SERVICE ALARM
ALARM VENT
SENSOR VENT
 
Fig. 3 
TESTING YOUR DETECTOR 
To test the detector (do not test when detector is at warm up 
mode), press the Test Button.   
  The red and orange LED's will flash and a sound will be 
heard 
MUTING YOUR DETECTOR 
You can partially mute the detector in an event of alarm by 
pressing the Test Button. The Red LED will continue to flash and a 
short beep will be heard every 16 seconds.   
Formatiert: Schriftartfarbe:
Automatisch