All parameters are specified at 24V, 80A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
19.6.  M
OUNTING 
O
RIENTATIONS
 
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in 
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction 
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous 
operation can be found below: 
Curve A1 
Recommended output current. 
Curve A2 
Max allowed output current (results in approximately half the lifetime expectancy of A1). 
 
Fig. 19-3 
Mounting 
Orientation  A 
(Standard 
orientation) 
YR80
Redundancy
Module
OUTPUT
INPUTS
 
Output Current
0
20
30
40
50
70°C
20
40
60
80A
60
A1
Ambient Temperature
 
 
 
 
Fig. 19-4 
Mounting 
Orientation  B 
(Upside down) 
YR80
Redundancy
Mo
dule
OUTPUT
INPUTS
 
Output Current
0
20
30
40
50
70°C
20
40
60
80A
60
A1
Ambient Temperature
 
 
 
 
Fig. 19-5 
Mounting 
Orientation  C  
(Table-top 
mounting) 
 
Output Current
0
20
30
40
50
70°C
20
60
80A
60
40
A1
A2
Ambient Temperature
 
 
 
 
Fig. 19-6 
Mounting 
Orientation  D  
(Horizontal cw) 
YR80
Redundancy
Modul
e
OUTPUT
INPUTS
 
Output Current
0
20
30
40
50
70°C
20
60
80A
60
40
A1
A2
Ambient Temperature
 
 
 
 
Fig. 19-7 
Mounting 
Orientation  E  
(Horizontal ccw) 
YR80
Redundancy
Modul
e
OUTPUT
INPUTS
 
Output Current
0
20
30
40
50
70°C
20
60
80A
60
40
A1
A2
Ambient Temperature
 
 
17/17