Puls DIMENSION YR80.241 din rail power supply U YR80.241 Datenbogen
Produktcode
YR80.241
YR80.241
Y-Series
24-28V,
80A,
D
UAL
R
EDUNDANCY
M
ODULE
Oct. 2010 / Rev. 1.0 DS-YR80.241-EN
All parameters are specified at 24V, 80A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
All parameters are specified at 24V, 80A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
19.6. M
OUNTING
O
RIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Recommended output current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 19-3
Mounting
Orientation A
(Standard
orientation)
Mounting
Orientation A
(Standard
orientation)
YR80
Redundancy
Module
OUTPUT
INPUTS
Output Current
0
20
30
40
50
70°C
20
40
60
80A
60
A1
Ambient Temperature
Fig. 19-4
Mounting
Orientation B
(Upside down)
Mounting
Orientation B
(Upside down)
YR80
Redundancy
Mo
dule
OUTPUT
INPUTS
Output Current
0
20
30
40
50
70°C
20
40
60
80A
60
A1
Ambient Temperature
Fig. 19-5
Mounting
Orientation C
(Table-top
mounting)
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
20
30
40
50
70°C
20
60
80A
60
40
A1
A2
Ambient Temperature
Fig. 19-6
Mounting
Orientation D
(Horizontal cw)
Mounting
Orientation D
(Horizontal cw)
YR80
Redundancy
Modul
e
OUTPUT
INPUTS
Output Current
0
20
30
40
50
70°C
20
60
80A
60
40
A1
A2
Ambient Temperature
Fig. 19-7
Mounting
Orientation E
(Horizontal ccw)
Mounting
Orientation E
(Horizontal ccw)
YR80
Redundancy
Modul
e
OUTPUT
INPUTS
Output Current
0
20
30
40
50
70°C
20
60
80A
60
40
A1
A2
Ambient Temperature
17/17