Finder 70.11.8.230.2022 Options: 1-phase mains monitoring (220 – 240 V/AC), undervoltage, overvoltage, over/under voltag 70.11.8.230.2022 Datenbogen

Produktcode
70.11.8.230.2022
Seite von 14
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
4b
UV
UVm*
Umax
Umax -H
LED 1
LED 2
LED 1
LED 2
4a
OV
OVm*
Umax
Umax -H
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
1
3a
3b
3d
3c
3e
3f
70.11
www.findernet.com
2
(1x6/2x4) mm
2
(1x10/2x12) AWG
(1x4/2x2.5) mm
2
(1x12/2x14) AWG
0.8 Nm
3
IP20
70.11.8.230.2022
U
N
: (220...240) V AC (50/60 Hz)
U
min
: 130 V AC
U
max
: 280 V AC
P: 2.6 VA / 0.8 W
1 CO (SPDT)
10 A 250 V AC
AC1                             2500 VA
AC15 (230 V AC)         750 VA
(230 V AC)         0.5 kW
DC1 (30 / 110 / 220)V   (10 / 0.3 / 0.12) A
(−20...+50) °C
IB7011001 - 08/12
4
4c
W
Wm*
1
~
M
NEDERLANDS
70.11 ENKELFASE NETSPANNING BEWAKINGSRELAIS
AFMETINGEN
AANSLUITSCHEMA
11-14: maakcontact
11-12: verbreekcontact
FRONTAANZICHT (detail)
3a
Functieschakelaar
UV
Onderspanning zonder geheugen
UVm Onderspanning met geheugen
OV
Overspanning zonder geheugen
OVm Overspanning met geheugen
W
Over- en onderspanning zonder geheugen
Wm Over- en onderspanning met geheugen
3b
LED 1 (groen)
3c
Uitschakelvertragingstijd (T op functiediagrammen) 
instelbaar (0.5...60)s
3d
LED 2 (rood)
3e
Maximum spanning instelknop (220...270)V
3f
Minimum spanning instelknop (170...230)V
FUNCTIES
4a
Onderspanning (UV en UVm functies)
4b
Overspanning (OV en OVm functies)
4c
Over- en onderspanning (W en Wm functies)
OPMERKING
Hysteresis (H op functiediagrammen): 5V.
Opstarttijd na aanbieden netspanning: 1s.
Inschakelvertragingstijd: 0.5s.
Positieve veiligheidslogica – Het maakcontact opent als het 
bewakingsrelais een fout detecteert.
*
RESET GEHEUGEN
Om te resetten, is het noodzakelijk om de netspanning UIT en 
daarna weer AAN te schakelen of draai de keuzeschakelaar 
naar een andere stand en vervolgens weer in de originele stand.
1
2
3
4