Duty cycle can be expressed, for example, as a 
percentage of the cycle time or as a relative quantity 
(such as 0 to 1000 or 0 to 10000). The pulse width can 
vary from 0 (no pulse, always off) to full scale (no 
pulse, always on).  
  Cycle time 
  Pulse width time 
The PWM output can be varied from 0 to full scale, providing a digital output that in many 
ways is the same as an analog output. For example, the PWM output can be used to control 
the speed of a motor from stop to full speed, or it can be used to control position of a valve 
from closed to fully opened.  
6.4 
Easy to create data logs 
Your control program can use the Data log instructions to store run-time data values in 
persistent log files. The data log files are stored in flash memory (CPU or memory card). Log 
file data is stored in standard CSV (Comma Separated Value) format. The data records are 
organized as a circular log file of a pre-determined size.  
The Data log instructions are used in your program to create, open, write a record, and close 
the log files. You decide which program values will be logged by creating a data buffer that 
defines a single log record. Your data buffer is used as temporary storage for a new log 
record. New current values must be programmatically moved into the buffer during run-time. 
When all of the current data values are updated, you can execute the DataLogWrite 
instruction to transfer data from the buffer to a data log record. 
You can open, edit, save, rename, and delete data log files from the File Browser page of 
the Web Server. You must have read privileges to view the file browser and you must have 
modify privileges to edit, delete, or rename data log files. 
Use the DataLog instructions to programmatically store run-time process data in flash 
memory of the CPU. The data records are organized as a circular log file of a pre-
determined size. New records are appended to the data log file. After the data log file has 
stored the maximum number of records, the next record written overwrites the oldest record. 
To prevent overwriting any data records, use the DataLogNewFile instruction. New data 
records are stored in the new data log file, while the old data log file remains in the CPU. 
Table 6- 21  DataLogWrite instruction 
LAD/FBD 
SCL 
Description 
 
"DataLogWrite_DB"( 
    req:=_bool_in_,  
    done=>_bool_out_,  
    busy=>_bool_out_, 
    error=>_bool_out_, 
    status=>_word_out_, 
    ID:=_dword_inout_); 
DataLogWrite writes a data record into the specified data log. 
The pre-existing target data log must be open.  
You must programmatically load the record buffer with current 
run-time data values and then execute the DataLogWrite 
instruction to move new record data from the buffer to the data 
log. 
If there is a power failure during an incomplete DataLogWrite 
operation, then the data record being transferred to the data log 
could be lost.