Easy to communicate between devices 
 
7.5 PROFINET 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
133
 
7.5 
PROFINET 
7.5.1 
Open user communication 
The integrated PROFINET port of the CPU supports multiple communications standards 
over an Ethernet network:                
●  Transport Control Protocol (TCP) 
●  ISO on TCP (RFC 1006) 
●  User Datagram Protocol (UDP) 
Table 7- 2 
Protocols and communication instructions for each 
Protocol 
Usage examples 
Entering data in the 
receive area 
Communication 
instructions 
Addressing type 
TCP  
CPU-to-CPU 
communication 
Transport of frames 
Ad hoc mode 
Only TRCV_C and 
TRCV 
Assigns port numbers to 
the Local (active) and 
Partner (passive) 
devices 
Data reception with 
specified length 
TSEND_C, TRCV_C, 
TCON, TDISCON, 
TSEND, and TRCV 
ISO on TCP 
CPU-to-CPU 
communication 
Message 
fragmentation and re-
assembly 
Ad hoc mode 
Only TRCV_C and 
TRCV 
Assigns TSAPs to the 
Local (active) and 
Partner (passive) 
devices 
Protocol-controlled 
TSEND_C, TRCV_C, 
TCON, TDISCON, 
TSEND, and TRCV 
UDP 
CPU-to-CPU 
communication 
User program 
communications 
User Datagram Protocol  TUSEND and TURCV  Assigns port numbers to 
the Local (active) and 
Partner (passive) 
devices, but is not a 
dedicated connection 
S7 communication  CPU-to-CPU 
communication 
Read/write data 
from/to a CPU 
Data transmission and 
reception with specified 
length 
GET and PUT 
Assigns TSAPs to the 
Local (active) and 
Partner (passive) 
devices 
PROFINET RT 
CPU-to-PROFINET 
IO device 
communication 
Data transmission and 
reception with specified 
length 
Built-in 