7.6 PROFIBUS 
 
Easy Book 
142
 
Manual, 03/2014, A5E02486774-AF 
Parameter 
Definition 
TSAP 
1
 and Subnet ID: 
ISO on TCP (RFC 1006) and S7 communication: Local and partner CPU 
TSAPs in ASCII and hexadecimal formats 
 
1
  When configuring a connection with an S7-1200 CPU for ISO-on-TCP, use only ASCII characters in the TSAP extension 
for the passive communication partners. 
Transport Service Access Points (TSAPs) 
Using TSAPs, ISO on TCP protocol and S7 communication allows multiple connections to a 
single IP address (up to 64K connections). TSAPs uniquely identify these communication 
end point connections to an IP address.  
In the "Address Details" section of the Connection Parameters dialog, you define the TSAPs 
to be used. The TSAP of a connection in the CPU is entered in the "Local TSAP" field. The 
TSAP assigned for the connection in your partner CPU is entered under the "Partner TSAP" 
field. 
Port Numbers 
With TCP and UDP protocols, the connection parameter configuration of the Local (active) 
connection CPU must specify the remote IP address and port number of the Partner 
(passive) connection CPU. 
In the "Address Details" section of the Connection Parameters dialog, you define the ports to 
be used. The port of a connection in the CPU is entered in the "Local Port" field. The port 
assigned for the connection in your partner CPU is entered under the "Partner Port" field. 
7.6 
PROFIBUS 
A PROFIBUS system uses a bus master to poll slave devices distributed in a multi-drop 
fashion on an RS485 serial bus. A PROFIBUS slave is any peripheral device (I/O 
transducer, valve, motor drive, or other measuring device) which processes information and 
sends its output to the master. The slave forms a passive station on the network since it 
does not have bus access rights, and can only acknowledge received messages, or send 
response messages to the master upon request. All PROFIBUS slaves have the same 
priority, and all network communication originates from the master.  
A PROFIBUS master forms an "active station" on the network. PROFIBUS DP defines two 
classes of masters. A class 1 master (normally a central programmable controller (PLC) or a 
PC running special software) handles the normal communication or exchange of data with 
the slaves assigned to it. A class 2 master (usually a configuration device, such as a laptop 
or programming console used for commissioning, maintenance, or diagnostics purposes) is 
a special device primarily used for commissioning slaves and for diagnostic purposes.