7.8 S7 communication 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
153
 
7.8 
S7 communication 
7.8.1 
GET and PUT instructions 
You can use the GET and PUT instructions to communicate with S7 CPUs through 
PROFINET and PROFIBUS connections. This is only possible if the "Permit access with 
PUT/GET communication" function is activated for the partner CPU in the "Protection" 
property of the local CPU properties:  
●  Accessing data in a remote CPU: An S7-1200 CPU can only use absolute addresses in 
the ADDR_x input field to address variables of remote CPUs (S7-200/300/400/1200). 
●  Accessing data in a standard DB: An S7-1200 CPU can only use absolute addresses in 
the ADDR_x input field to address DB variables in a standard DB of a remote S7 CPU. 
●  Accessing data in an optimized DB: An S7-1200 CPU cannot access DB variables in an 
optimized DB of a remote S7-1200 CPU. 
●  Accessing data in a local CPU: An S7-1200 CPU can use either absolute or symbolic 
addresses as inputs to the RD_x or SD_x input fields of the GET or PUT instruction, 
respectively. 
STEP 7 automatically creates the DB when you insert the instruction. 
 
 
Note 
To ensure data consistency, always evaluate when the operation has been completed 
(NDR = 1 for GET, or DONE = 1 for PUT) before accessing the data or initiating another 
read or write operation. 
 
 
Note 
V4.0 CPU program GET/PUT operation is not automatically enabled 
A V3.0 CPU program GET/PUT operation is automatically enabled in a V4.0 CPU. 
However, a V4.0 CPU program GET/PUT operation in a V4.0 CPU is not automatically 
enabled. You must go the CPU "Device configuration", inspector window "Properties"tab, 
"Protection" property to enable GET/PUT access (Page 82).