Easy to communicate between devices 
 
7.10 PtP, USS, and Modbus communication protocols 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
163
 
7.10 
PtP, USS, and Modbus communication protocols 
7.10.1 
Point-to-point communication 
The CPU supports the following Point-to-Point communication (PtP) for character-based 
serial protocols: 
●  PtP (Page 164) 
●  USS (Page 165) 
●  Modbus (Page 167) 
PtP provides maximum freedom and flexibility, but requires extensive implementation in the 
user program.  
 
 
PtP enables a wide variety of possibilities:  
 
The ability to send information directly to an external 
device such as a printer 
 
The ability to receive information from other devices 
such as barcode readers, RFID readers, third-party 
camera or vision systems, and many other types of 
devices 
 
The ability to exchange information, sending and 
receiving data, with other devices such as GPS 
devices, third-party camera or vision systems, radio 
modems, and many more 
This type of PtP communication is serial 
communication that uses standard UARTs to support a 
variety of baud rates and parity options. The RS232 
and RS422/485 communication modules (CM 1241) 
and the RS485 communication board (CB 1241) 
provide the electrical interfaces for performing the PtP 
communications. 
7.10.2 
Using the serial communication interfaces 
Two communication modules (CMs) and one communication board (CB) provide the 
interface for PtP communications:  
●  CM 1241 RS232 
●  CM 1241 RS422/485 
●  CB 1241 RS485 
You can connect up to three CMs (of any type) plus a CB for a total of four communication 
interfaces. Install the CM to the left of the CPU or another CM. Install the CB on the front of 
the CPU. Refer to the "Installation" chapter in the S7-1200 System Manual for detailed 
instructions on module installation and removal.