1.5 Mounting dimensions and clearance requirements 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
25
 
The S7-1200 equipment is designed to be easy to install. You can install an S7-1200 either 
on a panel or on a standard rail, and you can orient the S7-1200 either horizontally or 
vertically. The small size of the S7-1200 allows you to make efficient use of space.  
 
 
WARNING 
Installation requirements for S7-1200 PLCs 
The SIMATIC S7-1200 PLCs are Open Type Controllers. It is required that you install the 
S7-1200 in a housing, cabinet, or electric control room. Entry to the housing, cabinet, or 
electric control room should be limited to authorized personnel. 
Failure to follow these installation requirements could result in death, severe personal injury 
and/or property damage. 
Always follow these requirements when installing S7-1200 PLCs. 
 
Separate the S7-1200 devices from heat, high voltage, and electrical noise 
As a general rule for laying out the devices of your system, always separate the devices that 
generate high voltage and high electrical noise from the low-voltage, logic-type devices such 
as the S7-1200. 
When configuring the layout of the S7-1200 inside your panel, consider the heat-generating 
devices and locate the electronic-type devices in the cooler areas of your cabinet. Reducing 
the exposure to a high-temperature environment will extend the operating life of any 
electronic device. 
Consider also the routing of the wiring for the devices in the panel. Avoid placing low-voltage 
signal wires and communications cables in the same tray with AC power wiring and high-
energy, rapidly-switched DC wiring. 
Provide adequate clearance for cooling and wiring 
S7-1200 devices are designed for natural convection cooling. For proper cooling, you must 
provide a clearance of at least 25 mm above and below the devices. Also, allow at least 25 
mm of depth between the front of the modules and the inside of the enclosure. 
 
 
CAUTION 
For vertical mounting, the maximum allowable ambient temperature is reduced by 10 
degrees C.  
Orient a vertically mounted S7-1200 system as shown in the following figure. 
Ensure that the S7-1200 system is mounted correctly. 
 
When planning your layout for the S7-1200 system, allow enough clearance for the wiring 
and communications cable connections.